Kollmorgen SERVOSTAR 300 Serie Manuel page 51

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
2.4.9.2 Use as directed
The safety function STO is exclusively intended to provide functional safety, by preventing
the restart of a system. To achieve this functional safety, the wiring of the safety circuits
must meet the safety requirements of IEC 60204, ISO 12100, IEC 62061 SIL CL2 respect-
ively ISO 13849-1 PLd. If STO is automatically activated by a control system, then make
sure that the output of the control is monitored for possible malfunction.
2.4.9.3 Prohibited Use
The STO function must not be used if the drive is to be made inactive because of:
Cleaning, maintenance and repair operations, long inoperative periods:
In such cases, the entire system should be disconnected from the supply by the per-
sonnel, and secured (main switch).
Emergency-Off situations: the mains contactor must be switched off).
2.4.9.4 Technical data STO
Safety characteristic data
The subsystems (servo amplifiers) are totally described for safety technics with the char-
acteristic data :
Unit
STO-Enable
Pinout
Pin Signal
1,2 +24
3,4 DGND
5 STO-ENABLE STO Enable (Safe Torque Off)
Signal diagram
The diagram shows how to use STO function to ensure a safe stop of the drive and error free
operation of the servo amplifier.
Operation Mode EN 13849-1 EN 62061
single channel
PL d, Cat. 3
Description
+24 V DC auxiliary voltage supply,
20V..30V, 33mA – 40mA (Ieff), 100mA (Is)
24 V Supply GND
Kollmorgen | kdn.kollmorgen.com | November 2018
S300 Product Safety Guide | 2   English
PFH
[1/h]
[Years]
SIL CL 2
1.50E-07
T
SFF
M
[%]
20
100
51

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

S30361S30101S30301S30661S31061S30601

Table des Matières