Restore Rain Dial-R to Factory Default Settings

F
The Rain Dial-R factory default settings for automatic program
operation are as follows:
Current Time: 12:00 AM .
Current Day: Sunday .
Current Date: January 1, 2008 .
Program A: Weekday watering schedule with all days active .
One start time at 7:00 AM .
10-minute run time on all valve stations .
Program B and C: No watering days, station run times or start times .
Skip Days and Odd/Even day schedule: OFF - all Programs .
Excluded days in Skip Days or Odd/Even schedule: None .
MV/Pump operation: ON - all stations .
Well Recovery period: 00 (OFF) - all Programs .
MV/Pump operation during Well Recovery: OFF - all Programs .
Water Budget: 100% - all Programs and months .
Rain Delay: 0 days .
Stack/Overlap: Overlap - 3 Programs or 3 manual stations .
To restore factory default settings:
1 . Place the Function switch in the Set Program position .
2 . Place the Program switch to select Program B .
4 . Open the battery compartment and disconnect the battery .
3 . Leaving the AC power connected, carefully unplug the control
module ribbon cable from the terminal Board socket .
5 . Press and hold the Manual button .
6 . Plug in the ribbon cable and release the Manual button .
Note: With the dial in the Current Time position, the display
should now show 12:00 AM. If it does not, repeat the procedure
as necessary.
7 . Connect the battery .
8 . Reprogram the controller .