Positioning Of Outlet Terminals - Sime Planet Dewy 60 BFR Manuel De Montage, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.8
POSITIONING
OF OUTLET
TERMINALS (fig. 5)
The outlet terminal must be flush with the
wall and the inlet terminal must protrude
TABLE 1
MINIMUM DISTANCE
A - below openable window or door
B - below ventilation opening (non mechanical)
C - below eaves
D - below balcony (1)
E - from adjacent window or door
F - from adjacent ventilation opening (non mechanical)
G - from horizontal or vertical soil or drain pipes (2)
H - from corner of building
I - from recess in building
L - above a paved sidwalk or a paved driveway that is
located on private property
M - between two terminals set vertically
N - between two terminals set horizontally
O - from a surface facing without
openings or terminals
P - as above but with openings and terminals
Slanted view
50 mm (2 in) at least from the outstide
wall (fig. 5/a).
Outlet terminals for forced draft systems
may be located on the outer walls of the
buildings.
mm
feet
900
3
900
3
300
1
300
1
900
3
900
3
300
1
300
1
300
1
2100
7
600
2
600
2
2000
6.56
3000
9.84
Table 1 shows approximate, non-binding
minimum distances to be met for a building
of the type shown in fig. 5.
Please refer to local codes for minimum
clearances.
To install the tubes in such way protect the
building materials from degradation by fluegas.
1. The vent shall not terminate;
a) directly above a sidewalk or paved driveway that is located
between two single - family dwellings and severs both dwellings;
b) less that 2. 1 m (7 ft) above a paved sidewalk or a paved driveway
that is located on public property;
c) within 1.8 m (6 ft) of a mechanical air-supply inlet to any building;
d) above a meter and regulator assembly within 1.8 m (6 ft) horizon-
tally of the vertical centerline of the regulator vent outlet to a
maximum vertical distance of 4.5 m (15 ft);
e) within 1.8 m (6 ft) of any gas service regulator vent outlet;
f) less than 300 mm (1ft) above grade level plus expected snow
level;
g) within 900 mm (3 ft) of a window or door that can be opened in
any building, of any non-mechanical air supply inlet to any building,
or of any combustion air inlet of any other appliance;
h) Underneath a veranda, porch, or deck unless;
i) the veranda, porch, or deck is fully open on a minimum of two
sides beneath the floor;
ii) the distance between the top of the vent termination and the
underside of the veranda, porch, or deck is greater that 300 mm
(1ft).
2. When setting terminals, where materials that may be subject to the
action of the combustion products are present in the vicinity, e.g.,
eaves, gutters and downspouts painted or made of plastic material,
projecting timberwork, etc., distances of not less than 1.5 m (5 ft)
must be adopted, unless adequate shielding is provided to guard
these materials.
Frontal view
ENG
FR
Fig. 5
Fig. 5/a
9

Publicité

Chapitres

Table des Matières
loading

Table des Matières