Chaudières murales à basse température
Low temperature wall mounted boiler
Brava Slim BF
MANUEL POUR L'UTILISATION, L'INSTALLATION ET L'ENTRETIEN
USER, INSTALLATION AND SERVICING INSTRUCTIONS
FR
EN
Pour consulter la documentation,
visitez notre site web www.sime.it
To consult the documentation, visit our
website www.sime.it
Fonderie SIME S.p.A.
6328417 - 01/2022 - R1
TRADUCTION DES INSTRUCTIONS ORIGINALES - TRANSLATION OF THE ORIGINAL INSTRUCTIONS

Publicité

Table des Matières
loading

Sommaire des Matières pour Sime Brava Slim 25 BF

  • Page 1 Low temperature wall mounted boiler Brava Slim BF MANUEL POUR L’UTILISATION, L’INSTALLATION ET L’ENTRETIEN USER, INSTALLATION AND SERVICING INSTRUCTIONS Pour consulter la documentation, visitez notre site web www.sime.it To consult the documentation, visit our website www.sime.it Fonderie SIME S.p.A. 6328417 - 01/2022 - R1...
  • Page 2 - fermez les robinets du combustible et de l'eau de l'installation hydrique. – se réserve le droit Fonderie SIME S.p.A. de modifier à tout moment et sans pré- – Afin d'assurer une efficacité optimale avis ses propres produits afin de les...
  • Page 3: L'usage De L'appareil Par Des Enfants

    INTERDICTIONS IL EST INTERDIT IL EST INTERDIT – L’usage de l'appareil par des enfants – Boucher l'évacuation de la condensation d'âge inférieur à 8 ans. L’appareil peut (si présent). être utilisé par enfants d'un âge non infé- – Tirer, détacher, tordre les câbles élec- rieur à...
  • Page 4: Instructions Pour L'utilisation

    Cher client, STRUCTURE DU MANUEL Nous vous remercions d'avoir acheté une chaudière Sime Brava Ce manuel est organisé de la façon indiquée ci-dessous. , un appareil modulant à basse température, de dernière Slim BF génération, avec des caractéristiques techniques et des perfor-...
  • Page 5: Table Des Matières

    Codes anomalies / pannes ......8 4.2.2 Brava Slim 25 BF ÷ Brava Slim 30 BF ..9 1.6.1...
  • Page 6: Opérer Avec La Chaudière Brava Slim Bf

    OPÉRER AVEC LA CHAUDIÈRE BRAVA SLIM BF Panneau de commandes Bouchon de protection du connecteur de programmation. REMARQUE: la pression de plus de 30 secondes d'une touche quel- conque génère l'affichage d'une anomalie, sans interrompre le fonctionnement de la chaudière. Le signal disparaît dès le rétablis- sement de conditions normales.
  • Page 7: Contrôles Préliminaires

    Contrôles préliminaires – sélectionnez le mode de fonctionnement « ÉTÉ” en appuyant pendant au moins 1 seconde sur la touche . L'afficheur indi- quera la valeur de la sonde de départ mesurée à ce moment ATTENTION – Si nécessaire, accédez aux zones situées dans la partie inférieure de l'appareil, assurez-vous que les tempéra- tures des composants ou des conduits de l'installation ne soient pas élevées (danger de brûlures).
  • Page 8: Codes Anomalies / Pannes

    1.6.1 Demande d'entretien Codes anomalies / pannes Lorsqu'il sera nécessaire d'effectuer l'entretien de la chaudière, le Si durant le fonctionnement de la chaudière se présente une ano- symbole s'affichera. malie/panne, l'afficheur indiquera l'inscription « ALL » suivie du code anomalie. En cas d'alarme «...
  • Page 9: Extinction À Long Terme

    L'afficheur indiquera «- - » ÉLIMINATION 4.2.2 ÷ Brava Slim 30 BF Brava Slim 25 BF L'appareil et les équipements électriques et élec- troniques, provenant de contextes professionnels ou classifiables comme déchet domestique, en fin de vie, doivent être éliminés, conformément à...
  • Page 11 5.4.1 Brava Slim 25 BF - Brava Slim 30 BF..13 5.11 Schéma électrique ......18 5.4.2...
  • Page 12: Description De L'appareil

    Les choix conceptuels prin- lage et indique le code, le numéro de série de la chaudière et le cipaux que Sime a fait pour les chaudières Brava Slim BF sont : code-barres – le brûleur atmosphérique combiné à un corps d'échange en Plaque Technique: est située à...
  • Page 13: Structure

    Structure 5.4.1 Brava Slim 25 BF - Brava Slim 30 BF Ventilateur Sonde double (départ/sécurité thermique) Chambre de combustion Électrode allumage/détection Vanne de déviation Groupe de chargement de l'installation Sonde sanitaire Panneau de commandes Échangeur secondaire Vanne de gaz Filtre sanitaire et régulateur de débit Soupape de sécurité...
  • Page 14: Brava Slim 40 Bf

    5.4.2 Brava Slim 40 BF Ventilateur Sonde double (départ/sécurité thermique) Chambre de combustion Électrode allumage/détection Vanne de déviation Groupe de chargement de l'installation Sonde sanitaire Panneau de commandes Échangeur secondaire Vanne de gaz Filtre sanitaire et régulateur de débit Soupape de sécurité de l'installation Évacuation de la chaudière Pompe de l'installation Transducteur de pression de l'eau...
  • Page 15: Caractéristiques Techniques

    Caractéristiques techniques DESCRIPTION Brava Slim 25 BF Brava Slim 30 BF Brava Slim 40 BF CERTIFICATION Pays de destination DZ - TN Combustible G20 - G30/G31 Numéro PIN 1312CP5935 Catégorie II2H3+ B22P - B32P - B52P Type C12 - C12X - C32 - C32X - C42 - C42X - C52 - C52X...
  • Page 16: Circuit Hydraulique Principal

    Circuit hydraulique principal 0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C 0°C 27279 26135 25044 24004 23014 22069 21168 20309 19489 18706 10°C 17959 17245 16563 15912 15289 14694 14126 13582 13062 12565 20°C 12090 11634 11199 10781 10382 9999 9633...
  • Page 17: Panneau De Commandes

    la pression de plus de 30 secondes d'une touche quel- REMARQUE: 5.10 Panneau de commandes conque génère l'affichage d'une anomalie, sans interrompre le fonctionnement de la chaudière. Le signal disparaît dès le rétablis- sement de conditions normales. AFFICHEUR . Le symbole est présent en mode de fonctionne- «...
  • Page 18: Schéma Électrique

    5.11 Schéma électrique BRUN SAUX BLUE NOIR 3 2 1 NOIR BRUN BLUE CN12 CN13 CN15 CN14 CN11 Ligne Débitmètre Neutre Vanne de déviation Fusible (3.15AT - 250V) Transducteur de pression Transformateur d'allumage Thermostat d'Ambiance TA-TA2 Pompe de l'installation Sonde Externe Ventilateur Sonde Auxiliaire SAUX...
  • Page 19 INSTRUCTIONS POUR L'INSTALLATION ET L'ENTRETIEN SOMMAIRE iNSTallaTiON ENTrETiEN Réception du produit ......20 Règlementations .
  • Page 20: Installation

    INSTALLATION AVERTISSEMENTS Brava Slim BF Description Les opérations d'installation de l'appareil doivent être effectuées exclusivement par le Service Technique Sime L (mm) ou par le Personnel Professionnellement Qualifié avec P (mm) des protections appropriées pour l'OBLIGATION de porter H (mm) la prévention des accidents.
  • Page 21: Nouvelle Installation Ou Installation À La Place D'un Autre Appareil

    Si l'ancien générateur a déjà été enlevé ou est indisponible, rempla- ZONES DE RESPECT INDICATIVES cez-le par une pompe afin de faire circuler l'eau dans l'installation et procédez comme il est décrit ci-dessus. ≥ 5 Une fois le nettoyage effectué, avant l'installation du nouvel appa- reil, il est conseillé...
  • Page 22: Raccordements Hydrauliques

    65 65 65 65 peuvent être transformés pour fonctionner avec G30/G31 en utili- sant le « kit de buses spécifique » (en option) fourni par Sime , sur demande, séparément de la chaudière. En cas de transformation du gaz utilisé, effectuez entièrement la phase de «...
  • Page 23: Évacuation Des Fumées Et Aspiration De L'air Comburant

    Les chaudières Brava Slim BF doivent être dotées de conduits pour l'évacuation des fumées et l'aspiration de l'air comburant opportuns. Ces conduits doivent être considérés partie intégrante de la chaudière et sont fournis par Sime en kits accessoires, à commander séparément de l'appareil en fonction des types autorisés et des exigences d'installation.
  • Page 24: Conduits Coaxiaux (Ø 60/100Mm Et Ø 80/125Mm)

    Kit de bagues interne et externe 8091500 caractéristiques suivantes : Terminal d'aspiration 8089500 – Brava Slim 25 BF : diaphragme Ø 79 mm Coude à 45° M-F (6 pièces) 8077411 – Brava Slim 30 BF : diaphragme Ø 81 mm Récupération condensation L. 135 mm 8092800 –...
  • Page 25: Séparateur

    à 90° en aspiration, de respecter une dis- tance minimum du conduit de 0,50 m. Exemple de calcul des pertes de charge d'une chaudière Brava Slim 25 BF . Perte de charge (mm H Fig. 25 Accessoires Ø...
  • Page 26: Branchements Électriques

    III doit être prévu, conformément aux règles d'installation. En cas de remplacement, la pièce de rechange doit être demandée à Sime . Seuls les raccordements des composants optionnels, indiqués dans le tableau et à commander séparément de la chaudière, sont donc nécessaires.
  • Page 27: Sonde De Température Externe

    AVERTISSEMENTS 6.12.2 Chronothermostat ou Thermostat d'ambiance Il est obligatoire : Le branchement électrique du chronothermostat ou du thermostat – l'utilisation d'un disjoncteur omnipolaire, sectionneur d'ambiance a été précédemment décrit. Pour le montage du com- de ligne, conforme aux Normes EN (ouverture des posant dans la pièce à...
  • Page 28: Remplissage Et Vidage

    Installation MULTIZONE - avec pompes, thermostats d'ambiance Circuit sanitaire : et sonde externe. – ouvrez le robinet d'arrêt du circuit sanitaire (si prévu) – ouvrez un ou plusieurs robinets de l'eau chaude pour remplir et purgez le circuit sanitaire – une fois la purge effectuée, refermez les robinets de l'eau chaude. Circuit de chauffage : –...
  • Page 29: Opérations De Vidage

    6.13.2 Opérations de VIDAGE Circuit sanitaire : – fermez le robinet d'arrêt du circuit sanitaire (prévu lors de l'ins- tallation) – ouvrir deux ou plusieurs robinets de l'eau chaude pour vider le circuit sanitaire. Chaudière : – desserrez le bouchon du purgeur automatique (3) –...
  • Page 30: Mise En Service

    MISE EN SERVICE – En présence d'anomalie, l'afficheur indiquera l'inscription « Opérations préliminaires , le code anomalie (ex. « 06 » - absence de détection de la ALL » flamme) et l'inscription ATTENTION – Si nécessaire, accédez aux zones situées dans la partie inférieure de l'appareil, assurez-vous que les tempéra- tures des composants ou des conduits de l'installation ne soient pas élevées (danger de brûlures).
  • Page 31: Liste Des Paramètres

    Après avoir modifié toutes les valeurs des paramètres d'intérêt, – appuyez sur la touche pour faire défiler la liste des paramètres pour sortir du menu, appuyez simultanément , pendant ~ 5 s, sur les vers le haut et successivement sur pour faire défiler la liste touches jusqu'à...
  • Page 32 Unité de Type N° Description Plage Par défaut mesure 0 = selon TA 1 = TA antigel Fonctionnalité TA auxiliaire 2 = circuit sanitaire désactivé Retard de l'activation de la Vanne de Zone / Pompe de Gavage 0 .. 99 Retard activation DHW avec solaire 0 ..
  • Page 33: Affichage Des Données De Fonctionnement Et Des Compteurs

    TABLEAU D'AFFICHAGE INFO Affichage des données de fonctionnement et des compteurs Unité de Type N° Description Plage mesure Une fois que la chaudière fonctionne, il est possible pour le tech- Affichage de la version nicien autorisé de visualiser les données de fonctionnement et les compteurs en procédant ainsi :.
  • Page 34: Vérifications Et Réglages

    Vérifications et réglages 7.6.1 Fonction ramonage La fonction ramonage est utile au technicien de maintenance quali- fié pour vérifier la pression du gaz sur les buses, pour contrôler les paramètres de combustion et mesurer le rendement de combustion requis par la règlementation en vigueur. La durée de cette fonction est de 15 minutes et pour l'activer, veuil- lez opérer de la façon suivante : –...
  • Page 35: Réglage De La Pression Du Gaz Sur Les Buses

    Réglage de la pression Max du gaz : – appuyez sur la touche > pour faire à nouveau fonctionner la chau- – appuyez sur la touche et réglez le VALEUR D'EAU CHAUDE dière à la puissance maximale. Si les valeurs de pression du gaz SANITAIRE à...
  • Page 36: Changement Du Gaz Utilisable

    Les modèles Brava Slim BF peuvent être transformés du fonction- nement G20 au fonctionnement G30/G31 en installant les « Kits buses pour G30/G31 (GPL), code 5144716 (pour Brava Slim 25 BF ), 5144713 (pour Brava Slim 30 BF ) et code 5144725 (pour Brava Slim ) qui doivent être commandés séparément de la chaudière.
  • Page 37: Procédure De Réglage Automatique

    – vissez les contre-écrou (10) et le boulon (9) en interposant le joint Procédure de réglage automatique d'étanchéité Cette procédure DOIT TOUJOURS ÊTRE EFFECTUÉE lors du premier – remontez l'électrode (8) en plaçant son extrémité AU CENTRE de allumage, en cas de changement de gaz et après le remplacement : la rampe du brûleur (*) –...
  • Page 38 – maintenez enfoncée la touche et faites défiler les paramètres – appuyez sur la touche > pour modifier la valeur « 5 » jusqu'à atteindre le paramètre « 03 » – la valeur modifiée sera automatiquement mémorisée – appuyez sur la touche >...
  • Page 39: Fonction Confort Sanitaire (Préchauffage)

    Réglage de la pression Min du gaz : Installations avec évacuations des fumées CONCENTRIQUES – appuyez 2 fois sur la touche , l'afficheur indique « P00 » Pression sur les buses (mbar) Pouvoir Modèle Calorifique 12,5 - 12,9 27,8 - 28,2 35,8 - 36,2 Brava Slim 25 BF...
  • Page 40: Entretien

    ENTRETIEN Règlementations Nettoyage interne Pour un fonctionnement efficace et régulier de l'appareil, il est 8.3.1 Nettoyeur de l'échangeur préférable que l'Utilisateur emploie un Technicien Professionnelle- ment Qualifié afin que ce dernier se charge, avec une périodicité Pour effectuer le nettoyage de l'échangeur : , de son entretien.
  • Page 41: Nettoyage Du Brûleur

    – dévissez les quatre vis (5) et enlevez le panneau avant (6) de la 8.3.4 Opérations finales chambre de combustion en opérant avec précaution afin de ne Après avoir achevé le nettoyeur de l'échangeur et du brûleur : pas endommager le joint d'étanchéité et l'isolation du panneau –...
  • Page 42: Entretien Extraordinaire

    Entretien extraordinaire Type N° Anomalie Remède - Vérifier la rotation du rotor de En cas de remplacement de la carte électronique IL EST OBLIGA- la pompe TOIRE de programmer les paramètres comme il est indiqué dans le Absence de circulation de - Vérifier les branchements tableau et dans l'ordre indiqué.
  • Page 43: Demande D'entretien

    Type N° Anomalie Remède Type N° Anomalie Remède Erreur limite inférieure - Vérifiez la vanne à gaz et - Vérifiez l'électrode courant EV2 SGV la carte Erreur incapacité - Vérifiez les évacuations Panne le long de la d'atteindre le set de - Vérifiez le diaphragme de ligne logique de com- - Vérifiez la vanne à...
  • Page 44 Sime – reserves the right Fonderie SIME S.p.A. maintenance and checks are carried to make improvements to its products ONCE A YEAR at any time without prior notice, without – If the power cable is damaged, replace...
  • Page 45 RESTRICTIONS IT IS FORBIDDEN IT IS FORBIDDEN – To allow children under the age of 8 to – To block the condensate drain (if pres- use the appliance. The appliance can ent). be used by children no younger than – To pull, detach or twist the electrical ca- 8 years old, by people with physical or bles coming out of the appliance even if cognitive disabilities, and by people...
  • Page 46 Dear Customer, MANUAL STRUCTURE Thank you for purchasing a Sime Brava Slim BF boiler, a new-gen- This manual is organized as follows. eration low-temperature modulating device possessing technical and performance characteristics capable of satisfying your space heating and instant domestic hot water requirements with the ut- USER INSTRUCTIONS most safety and with limited running costs.
  • Page 47 Fault / malfunction codes ......50 4.2.2 Brava Slim 25 BF ÷ Brava Slim 30 BF ..51 1.6.1...
  • Page 48: Using The Boiler Brava Slim Bf

    USING THE BOILER BRAVA SLIM BF Control panel Programming connector cover plug. pressing any one of these buttons for more than 30 sec- NOTE: onds generates a fault on the display without preventing boiler operation. The warning disappears when normal conditions are restored.
  • Page 49: Preliminary Checks

    Preliminary checks – select the "SUMMER" operating mode by pressing and holding the button for at least 1 second. the value of the delivery sensor detected at that moment will appear on the WARNING display – Should it be necessary to access the areas in the bot- tom part of the appliance, make sure that the system components and pipes are not hot (risk of burning).
  • Page 50: Fault / Malfunction Codes

    1.6.1 Maintenance request Fault / malfunction codes When it is time to perform maintenance on the boiler, the If a fault/malfunction is detected during boiler operation, the symbol shows on the display. message "ALL" will appear on the display followed by the fault code.
  • Page 51: Shutting Down For Long Periods

    "- -" will appear on the display DISPOSAL 4.2.2 Brava Slim 25 BF ÷ Brava Slim 30 BF At the end of their life span, the appliance and electrical and electronic devices coming from...
  • Page 53 5.4.1 Brava Slim 25 BF - Brava Slim 30 BF..55 5.11 Wiring diagram ....... . 60 5.4.2...
  • Page 54: Description Of The Appliance

    Sime has produced for heating and domestic hot this is located on the outside of the packag- Packaging label: water production. The main design choices made by Sime for the ing and provides a code, the serial number of the boiler and boilers are:...
  • Page 55: Structure

    Structure 5.4.1 Brava Slim 25 BF - Brava Slim 30 BF Dual sensor (thermal safety/delivery) Combustion chamber Ignition/detection electrode Diverter valve System filling unit Domestic hot water sensor Control panel Secondary heat exchanger Gas valve Domestic water filter and flow regulator...
  • Page 56: Brava Slim 40 Bf

    5.4.2 Brava Slim 40 BF Dual sensor (thermal safety/delivery) Combustion chamber Ignition/detection electrode Diverter valve System filling unit Domestic hot water sensor Control panel Secondary heat exchanger Gas valve Domestic water filter and flow regulator System relief valve Boiler drain System pump Water pressure transducer Automatic bleed valve...
  • Page 57: Technical Features

    Technical features DESCRIPTION Brava Slim 25 BF Brava Slim 30 BF Brava Slim 40 BF CERTIFICATIONS Country of intended installation DZ - TN Fuel G20 - G30/G31 PIN number 1312CP5935 Category II2H3+ B22P - B32P - B52P Type C12 - C12X - C32 - C32X - C42 - C42X - C52 - C52X...
  • Page 58: Main Water Circuit

    Main water circuit 0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C 0°C 27279 26135 25044 24004 23014 22069 21168 20309 19489 18706 10°C 17959 17245 16563 15912 15289 14694 14126 13582 13062 12565 20°C 12090 11634 11199 10781 10382 9999 9633...
  • Page 59: Control Panel

    pressing any one of these buttons for more than 30 sec- NOTE: 5.10 Control panel onds generates a fault on the display without preventing boiler operation. The warning disappears when normal conditions are restored. DISPLAY “SUMMER” . This symbol appears when the boiler is oper- ating in "Summer"...
  • Page 60: Wiring Diagram

    5.11 Wiring diagram BROWN SAUX BLUE BLACK 3 2 1 BLACK BROWN BLUE CN12 CN13 CN15 CN14 CN11 Line Flow meter Neutral Diverter valve Fuse (3.15AT - 250V) Pressure transducer Ignition transformer TA-TA2 Air thermostat System pump External sensor Auxiliary sensor SAUX Ignition / Detection electrode Remote control (instead of air thermo-...
  • Page 61 INSTALLATION AND SERVICING INSTRUCTIONS TABLE OF CONTENTS iNSTallaTiON maiNTENaNCE Receiving the product ......62 Adjustments.
  • Page 62: Installation

    INSTALLATION CAUTION Brava Slim BF Description The appliance must only be installed by the Sime Tech- nical Service or by qualified professionals who MUST W (mm) suitable protective safety equipment. wear D (mm) H (mm) Receiving the product Weight (kg)
  • Page 63: New Installation Or Installation Of A Replacement Appliance

    If the old generator has already been removed or is not available, APPROXIMATE MINIMUM DISTANCES replace it with a pump to circulate water in the system and then proceed as described above. ≥ 5 Once cleaning operations have been carried out and before in- stalling the new appliance, it is recommended that a fluid is add- ed to the water system to protect it from corrosion and deposits.
  • Page 64: Plumbing Connections

    G30/G31 using the "specific nozzle kit" (optional) 65 65 65 65 provided by Sime on request separately from the boiler. If changing the type of gas to be used, carry out the entire "GAS phase of the appliance.
  • Page 65: Smoke Outlet And Combustion Air Inlet

    These ducts are considered Brava Slim BF an integral part of the boiler and are provided by Sime as an accessory kit, to be ordered separately from the appliance on the basis of the type permitted and the system requirements.
  • Page 66: Coaxial Duct (Ø 60/100Mm And Ø 80/125Mm)

    Boilers leave the factory equipped with a diaphragm (1) with the point) following characteristics: Wall outlet terminal 8089501 – Brava Slim 25 BF : diaphragm Ø 79 mm Internal and external ring nut kit 8091500 – Brava Slim 30 BF : diaphragm Ø 81 mm Inlet terminal 8089500 –...
  • Page 67 NOTE: minimum distance of 0.50 m of the duct is respected with a 90° inlet curve. Example: calculation of the load loss of a Brava Slim 25 BF boiler. Load loss (mm H Accessories Ø 80 Quan- Code Fig.
  • Page 68: Electrical Connections

    If this cable needs to be replaced, an original spare must be re- quested from Sime . Therefore only the connections of the original components as shown in the table are needed. These are to be ordered separate- ly from the boiler.
  • Page 69: External Temperature Sensor

    CAUTION 6.12.2 Chrono-thermostat or Air Thermostat It is compulsory: The electrical connection of the chrono-thermostat or air ther- – to use an omnipolar cut-off switch, disconnect mostat has already been described. When fitting the component switch, in compliance with EN standards (contact in the room where the readings are to be taken, follow the in- opening of at least 3 mm) structions provided on the packaging of the product itself.
  • Page 70: Refilling Or Emptying

    MULTI ZONE system - with pump, air thermostat and external Domestic hot water circuit: sensor. – open the isolation valves of the domestic hot water circuit (if present) – open one or more than one hot water valve to fill and bleed the domestic hot water circuit –...
  • Page 71: Emptying Operations

    6.13.2 EMPTYING operations Domestic hot water circuit: – close the domestic hot water circuit isolation valve (prear- ranged in installation) – open one or more than one hot water valve to fill and bleed the domestic hot water circuit. Boiler: –...
  • Page 72: Commissioning

    COMMISSIONING – if there is a fault, the message "ALL" will appear on the display, Preliminary operations the fault code (eg. "06" - no flame detected) and the message WARNING – Should it be necessary to access the areas in the bot- tom part of the appliance, make sure that the system components and pipes are not hot (risk of burning).
  • Page 73: List Of Parameters

    When all the parameter modifications have been made, exit the – press the button to scroll up the list of parameters and then parameter menu by pressing and holding down the buttons to scroll down the list for at least 5 seconds until the initial all at the same time screen is displayed.
  • Page 74 Type Description Range Step Default 0 = according to TA 1 = TA Antifreeze Auxiliary TA function 2= domestic hot water disabled Zone Valve / Pump Relaunch Delay 0 .. 99 DHW activation delay with solar power 0 .. 30 Anti-legionella Function (Only hot water tank) 50 ..
  • Page 75: Display Of Operating Data And Counters

    TABLE OF INFORMATION DISPLAYED Display of operating data and counters Type Description Range Step Once the boiler is operating a qualified technician can view the SW version operating data and the counters as follows:. External sensor - 9 .. 99 °C From the operating screen in the mode enabled at that moment Delivery sensor 1...
  • Page 76: Checks And Adjustments

    Checks and adjustments 7.6.1 Chimney sweeper function The chimney sweeper function is used by the qualified mainte- nance technician to check the gas pressure at the nozzles, detect the combustion parameters and to measure the combustion effi- ciency required by legislation in force. This function lasts 15 minutes and is activated by proceeding as follows: –...
  • Page 77: Adjusting Gas Pressure At The Nozzles

    Adjusting maximum gas pressure: – press the button > once again to make the boiler operate at – press button and set the DOMESTIC HOT WATER SET to maximum power. If the gas pressure values are correct it is maximum using the button >...
  • Page 78: Gas Conversion

    Brava Slim BF to operation with G30/G31 by installing the "Nozzle kit for G30/ G31 - code 5144716 (for Brava Slim 25 BF ), 5144713 (for Brava Slim 30 BF ) and code 5144725 (for Brava Slim 40 BF ) to be ordered sep- arately from the boiler.
  • Page 79: Automatic Calibration Procedure

    – tighten the counter-nut (10) and the swivel joint (9) and position Automatic calibration procedure the gasket This procedure MUST ALWAYS be performed when the appliance – refit the electrode (8) putting its end IN THE MIDDLE of the is first turned on, when the gas is changed and after replacing: burner element (*) –...
  • Page 80 – keep the button pressed and scroll through the parameters – press the button > to set the value at "5" until reaching parameter "03" – the modified value will be stored automatically – press the button > and select "1" (LPG) –...
  • Page 81: Domestic Hot Water Comfort Function (Preheating)

    Adjusting minimum gas pressure: Installation with CONCENTRIC smoke outlet – press the button twice, the message "P00" will appear on Pressure at nozzles (mbar) Heat Out- the display Model 12,5 - 12,9 27,8 - 28,2 35,8 - 36,2 Brava Slim 25 BF 1,7 - 2,0 3,1 - 3,4...
  • Page 82: Maintenance

    MAINTENANCE Adjustments Cleaning the inside of the appliance For the appliance to operate correctly and efficiently it is recom- 8.3.1 Cleaning the heat exchanger mended that the User calls upon the services of a Professionally Qualified Technician to carry out ANNUAL maintenance. To clean the heat exchanger: –...
  • Page 83: Cleaning The Burner

    – remove the four screws (3) and remove the front panel (4) from 8.3.4 Final operations the combustion chamber (6) working carefully so as not to After having cleaned the heat exchanger and the burner: damage the gasket or the panel insulation –...
  • Page 84: Unscheduled Maintenance

    Unscheduled maintenance Type Fault Solution - Check the rotation of the If replacing the electronic board , the user MUST set the parame- pump rotor ters as indicated in the table and in the sequence shown. No water circulating in - Check the electrical con- the system Setting for...
  • Page 85: Maintenance Request

    Type Fault Solution Type Fault Solution EV2 SGV current lower - Check electrode - Check gas valve and board limit error - Check outlets Combustion set cannot Fault on the valve - Check air diaphragm (for be reached error control logic line/valve - Check gas valve and board BF models) cable damaged...
  • Page 88 Fonderie Sime S.p.A - Via Garbo, 27 - 37045 Legnago (Vr) Tel. +39 0442 631111 - Fax +39 0442 631292 - www.sime.it...
  • Page 89 Fonderie Sime S.p.A - Via Garbo, 27 - 37045 Legnago (Vr) Tel. +39 0442 631111 - Fax +39 0442 631292 - www.sime.it...
  • Page 90 ‫العرب ي َّ ة‬ ‫العالج‬ ‫الع ُ طل‬ ‫رقم‬ ‫النوع ي َّ ة‬ ‫العالج‬ ‫الع ُ طل‬ ‫رقم‬ ‫النوع ي َّ ة‬ ‫افحص القطب الكهربا� أ‬ EV2 SGV ‫خطأ � ن ي الحد اال أ د� ن للتيار‬ ‫ي‬ ‫تح ق َّق من سالمة صمام الغاز والبطاقة‬ ‫افحص...
  • Page 91 ‫العرب ي َّ ة‬ ‫الصيانة الستثنائ ي َّ ة غ� ي العاد ي َّ ة‬ ‫العالج‬ ‫الع ُ طل‬ ‫رقم‬ ‫النوع ي َّ ة‬ ‫� ن ي حالة استبدال البطاقة ال إ لك� ت ون ي َّ ة يجب إل ز امي ًّ ا ضبط معاي� ي التشغيل كما هو موض َّ ح � ن ي الجدول وبالتسلسل‬ ‫تح...
  • Page 92 ‫العرب ي َّ ة‬ ‫فكّ لولبي ًّ ا اال أ ربعة ب ر اغي (5) ثم َّ ان ز َ ع ال ل َّ وحة اال أ مامي َّ ة (6) من غرفة االح� ت اق، مع العمل بحرص ح� ت ال‬ ‫عمل...
  • Page 93 ‫العرب ي َّ ة‬ ‫الصيانة‬ ‫النظافة الداخل ي َّ ة‬ ‫الضبط والتنظيم‬ ‫للتشغيل الفع َّ ال والمنتظ ِ م للجهاز ي ُ نص َ ح بأن يقوم المستخد ِ م بتكليف ف� ن ِّ ي مؤه َّ ل ومعتم َ د ليقوم‬ ‫سنو...
  • Page 94 ‫الطاقة الح ر ار ي َّ ة‬ ‫الموديل‬ Max ‫الحد اال أ قىص‬ 36,2 35,8 28,2 27,8 12,9 12,5 Brava Slim 25 BF min ‫الحد اال أ د� ن‬ 4,2 3,9 3,4 3,1 2,0 1,7 Max ‫الحد اال أ قىص‬...
  • Page 95 ‫العرب ي َّ ة‬ ‫استم ِ ر � ن ي الضغط عىل الز ِ ر‬ "03" ‫وانتق ِ ل ب� ي ن معاي� ي التشغيل ح� ت الوصول إىل معيار التشغيل‬ > "5" ‫لتعديل قيمة الضبط إىل‬ ‫اضغَ ك عىل الزر‬ ‫يتم...
  • Page 96 ‫العرب ي َّ ة‬ ‫إج ر اء المعا ي َ رة التشغيل ي َّ ة ال أ وتوماتيك ي َّ ة‬ ‫ارب ِ ط لولبي ًّ ا صامولة الحجز (01) والدو َّ ار (9)، مع وضع حشوة إحكام الغلق ومنع الت� ّ ب‬ )*( ‫أع...
  • Page 97 ‫ وذلك ب� ت كيب "طقم‬G30/G31 ‫ إىل‬G20 ‫ للعمل من نوعي َّ ة الغاز‬Brava Slim BF ‫يمكن تحويل الموديال َّ ت‬ 5144725 ‫ ) وكود‬Brava Slim 30 BF ‫ (لـ‬Brava Slim 25 BF (, 5144713 ‫، كود 6174415 (لـ‬G30/G31 ‫الفو َّ هات‬...
  • Page 98 ‫الموديل‬ Max ‫الحد اال أ قىص‬ 36,2 35,8 28,2 27,8 12,6 12,2 Brava Slim 25 BF min ‫الحد اال أ د� ن‬ 3,1 2,8 2,5 2,2 1,1 0,8 ‫ح� ت ق ر اءة قيم مستوي الضغط المذكورة � ن ي الجدول عىل مقياس الضغط‬...
  • Page 99 ‫العرب ي َّ ة‬ ‫الفحوصات وعمل ي َّ ات الضبط‬ ‫خاص ي َّ ة تنظيف المدخنة‬ 7.6.1 ‫الصيانة المؤه َّ ل للتح ق ُّق من مستوى ضغط غاز التشغيل � ن‬ ‫ة تنظيف المدخنة هذه مفيدة لف� ن‬ َّ ‫خاصي‬ ‫ِّ...
  • Page 100 ‫العرب ي َّ ة‬ INFO ‫جدول طريقة عرض البيانات‬ ‫عرض بيانات التشغيل والعد َّ ادات‬ ‫الخطوة‬ ‫وحدة القياس‬ ‫الن ِ طاق‬ ‫الوصف‬ ‫رقم‬ ‫النوع ي َّ ة‬ .: ‫بعد بدء عمل السخ َّ ان يمك ِ ن، للف� ن ِّ ي المختص، إظهار بيانات التشغيل والعد َّ ادات وذلك بالعمل كما يىل ي‬ sw ‫عرض...
  • Page 101 ‫العرب ي َّ ة‬ ‫الف� ت ا� ن‬ ‫الخطوة‬ ‫وحدة القياس‬ ‫الن ِ طاق‬ ‫الوصف‬ ‫رقم‬ ‫النوع ي َّ ة‬ ‫ي‬ ‫ ثا� ن‬TA = 0 ‫ي‬ ‫ ما ن ِ ع التجم ُّ د‬TA = 1 ‫ المساع ِ دة‬TA ‫الخاصي َّ ة التشغيلي َّ ة‬ ‫2 = ماء...
  • Page 102 ‫العرب ي َّ ة‬ ‫عقب االنتهاء من جميع التعديالت ال� ت ي ترغب فيها لقيم ضبط معاي� ي التشغيل، وللخروج من قائمة معاي� ي‬ ‫لالنتقال‬ ‫للدخول إىل قائمة معاي� ي التشغيل لزيادتها ثم َّ بعد ذلك اضغَ ط عىل‬ ‫اضغَ ط عىل الز ِ ر‬ ‫التشغيل،...
  • Page 103 ‫العرب ي َّ ة‬ ‫بدء التشغيل‬ "06" :‫" ، وكود هذا الخلل التشغيىل ي (مثال‬ALL" ‫� ن ي حالة وجود خلل تشغيىل ي ستظه ِ ر شاشة العرض الكتابة‬ ‫عمل ي َّ ات تحض� ي ي َّ ة‬ ‫عدم وجود الشعلة) والكتابة‬ ‫انتبه‬...
  • Page 104 ‫العرب ي َّ ة‬ ‫عمليات التفريغ‬ 6.13.2 :‫دائرة ماء الستخدامات الصح ي َّ ة الساخن‬ )‫أغل ِ ق محبس غلق دائرة ماء االستخدامات الصحي َّ ة الساخن (إذا ما ن ُ ص َّ عىل ذلك أثناء ال� ت كيب‬ .‫اف ت َ ح صنبور ماء واحد أو أك� ش من صنبور للماء الساخن لتفريغ دائرة ماء االستخدامات الصحي َّ ة الساخن‬ :‫السخَّ...
  • Page 105 ‫العرب ي َّ ة‬ :‫دائرة ماء الستخدامات الصح ي َّ ة الساخن‬ .‫شبكة تشغيل متعد ِّ دة المناطق - مع مضخَّ ات، وترموستاتات خارج ي َّ ة ومسبار ح ر ارة خارجي‬ )‫اف ت َ ح محبس غلق دائرة ماء االستخدامات الصحي َّ ة الساخن (إذا ما ن ُ ص َّ عىل ذلك‬ ‫اف...
  • Page 106 ‫العرب ي َّ ة‬ ‫تحذير‬ ‫الكرونوترموستات أو ترموستات البيئة المحيطة‬ 6.12.2 ‫توصيل الكرونوترموستات أوز ترموستات البيئة المحيطة بالتي َّ ار الكهر� ب ي سبق ذكره ووصفه ل� ت كيب مسبار الح ر ارة‬ :‫يجب إل ز امي ًّ ا‬ ‫استخدام قاطع تيار مغناطيس ي ح ر اري متعد ِّ د اال أ قطاب، أو قاط ِ ع تي َّ ار‬ .‫�...
  • Page 107 ‫) ح� ت تضعها � ن ي وضعي َّ ة أفقي َّ ة‬b( ‫ل ف َّها إىل اال أ مام‬ .‫ال� ت كيب‬ . Sime ‫� ن ي حالة استبدال هذا الكابل، يجب أن يتم ُّ طلب هذا االستبدال من � ش كة‬ ‫ة، المذكورة � ن‬...
  • Page 108 ‫مالحظة: الستخدام السخ َّ ان بالشكل الصحيح، بكوع توصيل ب ز اوية °09 � ن ي مجرى الشفط، يجب م ر اعاة واح� ت ام‬ . 0,50 m ‫الحد اال أ د� ن للمسافة الفاص ِ لة لال أ نبوب البالغة‬ . Brava Slim 25 BF ‫مسال لحساب نسب فاقد ضغط التحميل ال أ حد السخ َّ انات‬ )mm H O( ‫فاقد...
  • Page 109 :‫تأ� ت ي سخ َّ انات المياه من المص ن َ ع وهي مزو َّ دة بفاصل حجز (1) له المواصفات التالية‬ 8089500 ‫طرف شفط‬ Ø 79 mm ‫ : حاجز فصل‬Brava Slim 25 BF 8077411 )‫ °54 ق ِ ط َع‬M F )6 ‫كوع توصيل ز اوية‬...
  • Page 110 ‫ � ن ي أطقم الملحقات‬Sime ‫ مزو َّ دة بأنابيب مناسبة لطرد أدخنة االح� ت اق ولشفط الهواء الال َّ ز ِ م لالح� ت اق التشغيىل ي . ت ُ عت� ب َ هذه اال أ نابيب جزء ال...
  • Page 111 8075441 ) 40 kW( ‫صفيحة ال� ت كيب‬ 8075438 8075418 ‫طقم أكواع توصيل‬ 8075443 SIME ‫ إىل‬DIN ‫طقم أكواع توصيل وصناب� ي ذات وصالت من‬ 8091806 ‫طقم صناب� ي‬ 8075442 SIME ‫ إىل‬DIN ‫طقم صناب� ي ذات وصالت من‬ 8093900 ‫طقم...
  • Page 112 ‫العرب ي َّ ة‬ ‫� ن ي حالة أن َّ مو ل ِّ د الح ر ارة القديم قد سبقت إ ز الته أو أ ن َّ ه غ� ي موجود، فإ ن َّ ه يجب استبداله بمضخ َّ ة لتدوير المياه‬ .‫�...
  • Page 113 ‫الوصف‬ ‫ أو عىل‬Sime ‫يجب أن تتم عمليات تركيب هذا الجهاز فقط وح�يا عىل يد فن� ي ي الخدمة‬ ‫يد فني� ي ن متخصص� ي ن ومعتمدين مع � ن ورة الل� ت ن ام بارتداء أدوات الحماية من الحوادث‬...
  • Page 114 ‫العرب ي َّ ة‬ ‫إرشادات ال� ت كيب والصيانة‬ ‫فهرس‬ ‫ةنايصلا‬ ‫بيكرتلا‬ 40............. . ‫ميظنتلاو طبضلا‬ 20.
  • Page 115 ‫العرب ي َّ ة‬ ‫مخ ط َّ ط التوصيالت الكهربائ ي َّ ة‬ 5.11 SAUX 3 2 1 CN12 CN13 CN15 CN14 CN11 ‫ مقياس التد ف ُّق‬FLM ‫الخط‬ ‫ صمام التحويل‬VD ‫المحايد‬ ‫ محو ِّ ل مستوى الضغط‬TPA )3.15AT 250V( ‫المص ه َ ر الكهر� ب ي‬ ‫ترموستات...
  • Page 116 ‫العرب ي َّ ة‬ ‫مالحظة: الضغط عىل أي ز ِ ر لمد َّ ة 03 ثانية يؤ د ِّ ي إىل ظهور الخلل التشغيىل ي الموجود دون الحاجة إىل إيقاف‬ ‫لوحة مفاتيح التشغيل‬ 5.10 .‫السخ َّ ان عن العمل. تختفي إشارة التنبيه هذه عند اس� ت جاع ظروف التشغيل الطبيعي‬ ‫شاشة...
  • Page 117 ‫العرب ي َّ ة‬ ‫دائرة التشغيل الهيدروليك ي َّ ة ال أ ساس ي َّ ة‬ 0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C 0°C 27279 26135 25044 24004 23014 22069 21168 20309 19489 18706 10°C 17959 17245 16563 15912 15289...
  • Page 118 ‫العرب ي َّ ة‬ ‫المواصفات الفن ي َّ ة‬ ‫الوصف‬ BRAVA SLIM 40 BF Brava Slim 30 BF Brava Slim 25 BF ‫شهادة العتماد‬ DZ - TN ‫البلد المستهد َ ف‬ G20 - G30/G31 ‫غاز التشغيل‬ 1312CP5935 "PIN" ‫رقم التعريف‬...
  • Page 119 ‫العرب ي َّ ة‬ 5.4.2 Brava Slim 40 BF ‫المروحة‬ )‫المسبار المزدوج (الضخ الدفعي/اال أ مان الح ر اري‬ ‫غرفة االح� ت اق‬ ‫قطب اال إ شعال/الكشف الكهر� ب ي‬ ‫صمام التحويل‬ ‫مجموعة ملء الشبكة‬ ‫مسبار ماء االستخدامات الصحي َّ ة الساخن‬ ‫لوحة...
  • Page 120 ‫العرب ي َّ ة‬ ‫مكو ِّ نات الجهاز‬ Brava Slim 25 BF - Brava Slim 30 BF 5.4.1 ‫المروحة‬ )‫المسبار المزدوج (الضخ الدفعي/اال أ مان الح ر اري‬ ‫غرفة االح� ت اق‬ ‫قطب اال إ شعال/الكشف الكهر� ب ي‬ ‫صمام التحويل‬...
  • Page 121 ‫ملص َ ق البيانات التعريف ي َّ ة عىل علبة التغليف: موضوع عىل الجزء الخارجي من علبة التغليف ويحمل كود‬ : ‫ هي ما يىل ي‬Brava Slim BF ‫ لسخ َّ انات المياه‬Sime ‫اال أ ساسي َّ ة ال� ت ي انتقتها‬...
  • Page 122 13.........
  • Page 123 ‫العرب ي َّ ة‬...
  • Page 124 "- -" ‫ستظه ِ ر شاشة العرض‬ ‫التخ ل ُّ ص من الجهاز‬ Brava Slim 25 BF ÷ Brava Slim 30 BF 4.2.2 ‫يجب تسليم الجهاز ومثله اال أ جهزة الكهربائية واال إ لك� ت ونية القادمة من المنازل أو‬...
  • Page 125 ‫العرب ي َّ ة‬ ‫أكواد حالت الخلل التشغيىل ي / ال أ عطال‬ ‫طلب الصيانة‬ 1.6.1 ‫عند الوصول إىل الف� ت ة ال� ت ي يصب ِ ح فيها من ال� ن وري إج ر اء عملي َّ ة صيانة للسخ َّ ان فإ ن َّ ه عىل شاشة العرض‬ ‫"...
  • Page 126 ‫العرب ي َّ ة‬ )ESTATE( "‫اخ� ت َ طريقة التشغيل "الصيف‬ ‫فحوصات تحض� ي ي َّ ة‬ ‫. ستظه ِ ر شاشة‬ ‫، بالضغط لمد َّ ة 1 ثانية عىل الز ِ ر‬ ‫العرض قيمة مسبار الضخ الدفعي النا ت ِ جة � ن ي هذه ال ل َّ حظة‬ ‫انتبه‬...
  • Page 127 ‫العرب ي َّ ة‬ BRAVA SLIM BF ‫استخد ِ م السخَّ ان‬ ‫لوحة مفاتيح التشغيل‬ .‫غطاء من ف َذ موص ِّ ل ال� ب مجة‬ ‫مالحظة: الضغط عىل أي ز ِ ر لمد َّ ة 03 ثانية يؤ د ِّ ي إىل ظهور الخلل التشغيىل ي الموجود دون الحاجة إىل إيقاف‬ .‫السخ...
  • Page 128 9 ........
  • Page 129 ‫شكل ومحتويات دليل الستخدام‬ ‫ ، وهي جيل جديد من اال أ جهزة التضميني ّ ة منخفضة الح ر ارة‬Sime Brava Slim BF ‫نشكرك عىل � ش اء غالية‬ ‫المجهزة بكل الم� ي ن ات التقنية وم� ي ن ات اال أ داء ال� ت ي تل� ب ي احتياجاتك � ن ي تدفئة المكان وتسخ� ي ن الماء المخصص‬...
  • Page 130 ‫العرب ي َّ ة‬ ‫محظورات‬ ‫ممنوع‬ ‫ممنوع‬ 8 ‫استخدام الجهاز من ق ِ ب َ ل اال أ طفال اال أ قل من سن‬ .)‫غلق من ف َذ تفريغ التك ث ُّ فات (إذا كان موجو د ً ا‬ ‫سنوات. يمكن استخدام هذا الجهاز من ق ِ ب َ ل اال أ طفال‬ ‫شد...
  • Page 131 ‫الحاجة ويجب دائم ً ا أن ي ر افق الجهاز ح� ت � ن ي حالة‬ ‫ ال� ت ي غ� ي مسؤولة عن أ ي َّ ة‬Sime ‫الذي حد َّ دته له � ش كة‬ ‫أ� ن ار أو تلفيات قد تلحق باال أ شخاص أو الحيوانات‬...
  • Page 132 ‫دليل إرشادات االستخدام وال� ت كيب والصيانة‬ ‫العرب ي َّ ة‬ ‫لالطالع عىل دليل االستخدام وغ� ي ه من‬ : ‫المستندات، تفضل بزيارة موقعنا اال إ لك� ت و� ن ي‬ www.sime.it Fonderie SIME S.p.A. 6328417 - 01/2022 - R1 ‫اال إ رشادات اال أ صلية‬...

Table des Matières