3.2
TEMPERATURE
SENSOR AND WATER
PRESSURE
TRANSDUCER
Antifreeze system made up of the
NTC heating sensor that activates
when the water temperature reaches
6°C (42 °F).
Tables 3 - 3/a include the resistance
values (Ω) that are obtained on the
probe (SM) when the temperature
changes and those on the transducer
when pressure changes.
The module does not work when the
heating probe (SM) is cut off.
TABLE 3 (Sensors)
Temperature (°C/°F)
20/68
30/86
40/104
50/122
60/140
70/158
80/176
30
11
9
NOTE: To gain access to trimmers (6) and (10),
slide off the central heating potentiometer knob.
TABLE 3/a (Transducer)
3.3
Ignition and flame detection is con-
trolled by two electrodes located on
the burner. These guarantee maxi-
mum safety with intervention times,
for accidental switching off or gas fai-
lure, of within one second.
Resistance (Ω)
12.090
8.313
3.3. 1 Operating cycle
5.828
4. 1 61
Rotate the selector to summer or win-
3.021
ter and check the green led ( ) to
2.229
make sure power is on. The burner
1.669
10
X25
X4
13
17
6
Pressure
Resistance (Ω)
(bar)
mín
máx
0
297
320
0,5
260
269
1
222
228
1,5
195
200
2
167
173
2,5
137
143
3
108
113
3,5
90
94
ELECTRONIC IGNITION
6
10
8
KEY
1 Ignition electrode earth faston
3 Fuse (1,6 AT)
16
5 "ANN. RIT." connector
6 "POT. ACC." trimmer
8 D.H.W. potentiometer
9 Detector electrode faston
10 "POT. RISC." trimmer
11 C.H. potentiometer
12 Selector REMOTE/OFF/
/SUMMER/WINTER/RESET
13 DIP SWITCH
14 Connector "Modureg Sel."
15 Connector "Albatros"
16 Connector X25
17 Connector X4
should ignite within max. 10 seconds.
Failed ignition consequently lighting the
appliance block signal may occur due
to the following:
– Ignition electrode does not spark
Only gas is supplied to the boiler and,
after 10 sec., the block led turns on.
It may be caused by the fact that the
electrode is cut-off or is not secured
in the ignition transformer terminal.
– No flame detection
At ignition, the electrode continues
to spark even though the burner is
on. After 10 sec. it stops sparking,
the burner turns off and the block
led turns on.
The detection electrode wire is cut-
off or the electrode is grounded;
the electrode is worn and requires
replacement. The electronic board
is defective.
A sudden blackout immediately turned
off the burner, when power is restored,
the boiler will automatically start.
Fig. 13