Installing The Compressor; Installation Location; Vibration Dampers - Bitzer ORBIT 6 GSD60120 Instructions De Service

Compresseurs à scroll hermétiques
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 2: Lifting the ORBIT 8

4.2 Installing the compressor

4.2.1

Installation location

Install the compressor vertically. Maximum allowable
lateral tilt: 3°. For marine applications, please contact
BITZER.
ESB-130-7
For outdoor installation, take suitable measures to pro-
tect the compressor against corrosion (e.g. caused by
seawater or aggressive atmosphere) and low outside
temperatures. Lifting lugs and pipe connection points
should be coated with touch-up paint or suitable anti-
corrosion coasting after handling and installation to
minimize potential for unsightly surface rust. Consulta-
tion with BITZER is recommended.
4.2.2

Vibration dampers

To avoid noise and vibration transmission to the envir-
onment, it is recommended mounting all compressors
with damper elements.
For compound compressor units, the compressors
must be solidly mounted (without vibration damper) on
the fixing rails. Mount the vibration damper below the
fixing rails.
Tightening
ORBIT 6 + ORBIT 8
Type I for single compressors: Maximum joint preload:
21,351 N (4800 lbs)
Type II for tandem and trio: Maximum joint preload:
21,351 N (4800 lbs)
NOTICE
!
!
Do not mount the compressor solidly on the
heat exchanger!
Risk of damage to the heat exchanger (fatigue
fractures).