Instructional Booklet
Page 12
Effective: July 2008
UTILITY SENSING
CONNECTIONS
Figure 17. Connection of the Generator Utility Sensing Wires.
4.8 Preliminary Checks
After the ATS enclosure is installed and power cables are con-
nected to the equipment, thoroughly inspect the unit to ensure
that no tools were left inside and that the cabinet is free of debris.
If necessary, use a vacuum cleaner to remove any and all con-
struction or installation debris from the equipment.
Read and understand all labels on the equipment. Review and
understand the wiring diagrams supplied with the equipment.
Note any optional accessories that may have been furnished with
this unit and review their operation.
Verify that the phase-to-phase line voltages of both the utility and
generator power sources are the same and that they match the
rated voltage as indicated on the ATS ratings label.
SEVERE EQUIPMENT DAMAGE CAN RESULT IF THE UNIT IS NOT
APPLIED AT PROPER VOLTAGE. DO NOT ENERGIZE THE EQUIP-
MENT IF THE SUPPLY VOLTAGES DO NOT MATCH EQUIPMENT
RATINGS LABEL.
CAUTION
For more information visit: www.eaton.com
O & M Manual for the EGS Automatic
Transfer Switch with RTC-50 Control
4.9 Protection
For Catalog # EGS100 only
When protected by one of the following circuit breakers rated not
more than 150 amperes, this transfer switch is rated for use on a
circuit capable of delivering not more than 22,000 RMS symmetri-
cal amperes, 240 volts maximum, but not more than the interrupt-
ing capacity of the selected circuit breaker.
Eaton/Cutler-Hammer
BR
CH
FDC
BW
BWH
Siemens
CED6
ED6
ED4
When protected by circuit breakers without adjustable short-time
response only or by fuses this transfer switch is rated for use on a
curcuit capable of delivering not more than 10,000 RMS symmet-
rical amperes at 240V AC.
MANUFACTURER-ANY
BREAKER-ANY
TYPE-ANY
AMPS MAX-PER NEC
For Catalog #EGS100SE only
This switch is equipped with integral over-current protection.
Continuous load current not to exceed 80 percent of switch rat-
ing.
This Transfer Switch is rated for use on a circuit capable of deliv-
ering not more than 10,000 rms symmetrical amperes, 240 volts
maximum.
CSR
CSH
HED6
HED4