Troubleshooting

Checking the electrical safety
6
Troubleshooting
Malfunction
No current available from the
sockets
A low output voltage for
a zero load
A high output voltage for
a zero load
A low output voltage under
load
An uneven output voltage
Noisy operation
36
This section contains faults and problems which can be
removed by suitable persons during operation.
Each occurring problem is described with its possible cause
and the respective corrective measure.
The authorised personnel must immediately shut down the
generator and inform the responsible and authorised service
personnel if a problem cannot be solved with the aid of the
following table.
*A service station is recommended for performing these
checks or repairs
Possible cause
The machine speed is too low *Adjust the machine speed
Disconnected or short-
circuited cabling
Rotor or stator winding - open
circuit/short-circuited
The machine speed is too
low.
Rotor or stator winding open
circuit/short-circuited
The machine speed is too
high
The machine speed for full
load is too low
Too much load present
An uneven load present
Loose generator or machine
screws
Short-circuit in the generator
field/load
Correction
Check the consumers
*Test the winding resistance;
replace the winding if
necessary
*Adjust the machine speed
*Test the winding resistance;
replace the winding if
necessary
*Adjust the machine speed
*Adjust the machine speed
Reducing the existing load
Remove the whole load then
apply again individually in
order to establish which one
creates the uneven function.
Tighten all assembly parts
*Check the winding
resistance, replace the field
winding and check the loading
devices for a short-circuit if
necessary. Replace the
defective loading device.