8.4
pneumatic connection
DanGer!
danger – high pressure in the equipment!
▶ Before loosening the lines and valves, turn off the pressure and
vent the lines.
WarninG!
risk of injury from unsuitable connection hoses!
Hoses which cannot withstand the pressure and temperature
range may result in hazardous situations.
▶ Use only hoses which are authorised for the indicated pressure
and temperature range.
▶ Observe the data sheet specifications from the hose
manufacturers.
for control function i – danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If
the pressure fails, no defined position is reached.
▶ To ensure a controlled restart, first pressurize the device with
pilot pressure, then switch on the medium.
22
english
Type 2101
Installation
8.4.1 connection of the control medium
If the position of the pilot air ports for installation of the
hoses is unfavorable, these can be aligned steplessly by
rotating the actuator through 360°.
The procedure is described in the chapter entitled "8.3.3
Rotating the actuator".
Air discharge connection
CFA, CFB
Pilot air port CFI
Pilot air port
CFA, CFB, CFI
Fig. 17:
Pneumatic connection
control functions a and B:
→
Connect the control medium to the pilot air port 1 of the actuator
(see "Fig. 17").
Silencer
For the versions with a plug-in connection the silencer for reducing
the exhaust air noise is supplied loose.
→
Plug the silencer into the free air discharge connection 2
(see "Fig. 17").
If used in an aggressive environment, we recommend
conveying all free pneumatic connections into a neutral
atmosphere with the aid of a pneumatic hose.
2
1