Error message
Description
The inverter cannot or may not feed the grid at full power because the
Derating: 10
average output voltage over a period of 10 minutes has been outside the
minute average
value > 30 min
permissible tolerance range for over 30 minutes.
The inverter has received an external signal via the communications inter-
Derating: External
face and is currently feeding the grid at reduced power. This state has now
(e.g. Power Com-
pany) > 30 min
existed for more than 30 minutes.
The time and/or date have not been correctly set at the inverter. The in-
Time/date not set
verter operates without restrictions but the measurements are not correctly
stored in the internal data logger.
The communications card inserted into the inverter has signalled an error.
Option card fault
The communication to the outside world is possibly interrupted but the
inverter is otherwise operating without restrictions. Check the communica-
tion. The communications card may need to be reset (remove the card,
wait a minute and then re-install the card).
The inverter has fed no power into the grid for at least 24 hours.
No grid feed for
24 h
The output voltage between two or more phases of the inverter exceeds
Grid fault (island-
the permissible tolerance range. The inverter switches off for safety rea-
ing)
sons.
Self test failed.
Tab. 5:
Inverter error messages
Note the number of the affected inverter shown in the error message!
1)
Possible causes:
2)
• Internal communication fault
• Maximum permitted feed-in temperature exceeded
• Conductor breakage in power unit
Startup current limiting is active: 10 minute pause after more than 5 startup attempts in the last
3)
15 minutes.
734.144 | Z04 | 2012-11-22
Contact your installer if this warning occurs frequently.
Set the date and time.
Contact your installer if this error message persists.
Check if the DC switch is switched off or if snow is lying on the solar
modules. If neither is the case then contact your installer.
Contact your installer.
Perma-
Type
nent
W
W
I
X
I
X
E
X
E
X
E
X
51