SAmPleS of AlloWAble Plenum/duCTinG ArrAnGemenTS ConTinued
ALLOWABLE
"ADD ON"
WOOD
FURNACE
6.6
EmBEr STOP
○
for installations on combustible flooring an ember stop protective floor covering must be installed.
○
An ember stop of minimum 0.015" (0.4 mm) thick sheet steel extending 18" (457 mm) in front of firebox
door to 2" (76 mm) behind the cleanout of the chimney. The ember stop width must protrude a minimum of
8" (203 mm) from both sides of the furnace.
○
Carpet or other floor covering shall be removed before placement of ember stop sheet.
○
refer to Section 7.1 of CAn/CSA-b365-01 for complete details of floor protection.
EMBER STOP: SIDE DIMENSIONS
8"
(203 mm)
"ADD ON"
EXISTING
WOOD
FURNACE
FURNACE
DIVIDER
EXISTING
FURNACE
"ADD ON"
ELECTRIC
WOOD
FURNACE
FURNACE
(down ow
or counter ow)
8"
(203 mm)
EMBER STOP
PROHIBITED
"ADD ON"
WOOD
FURNACE
"ADD ON"
WOOD
FURNACE
"ADD ON"
WOOD
FURNACE
EMBER STOP: FRONT AND REAR DIMENSIONS
18"
(457 mm)
EMBER STOP
41
EXISTING
FURNACE
(down ow
or counter ow)
HORIZONTAL
EXISTING
FURNACE
HORIZONTAL
EXISTING
FURNACE
2"
(51 mm)
W415-1013 / A / 06.05.12