Secure all flag connectors to switch terminals, route ground line to switch chassis, and check that
jumper wire between line in and load has been installed.
Confirm limits on rotary dial as follows:
CAUTION
THe PreSeT vAlueS on THe fAn limiT
ConTrol muST noT be CHAnGed from
THe fACTory SeTTinG.
Any AdJuSTmenT To THiS ConTrol Will
AffeCT THe oPerATinG effiCienCy
of THe furnACe And Will void THe
WArrAnTy CoverAGe.
once set point limits have been confirmed, carefully manipulate wiring inside wood limit connection
box so that installation of connection box cover does not disturb or impede mechanical set point tabs
and rotary dial.
FOR FURNACE THAT IS NOT AC READY
for furnaces that are not AC ready a fan control centre must be added to the original furnace.
BLOWER
"LINE"
TERMINAL
BLOWER
NEUTRAL
L1
N
COM
R
WHITE
NEUTRAL
BLACK / YELLOW
RED
FAN OFF
SET pOINT
115°F (46°C)
THiS STeP iS for "Add-on"
ConfiGurATion only!
RELAY FROM LOWER
ELECTRICAL BOX ON
HMF150/200
G
WHITE ROGERS
FAN CONTROL CENTRE
8A05A-101
21
HIgH LIMIT SET pOINT
250°F (121°C),
(NOT TO BE MOvED
FROM THIS pOSITION!)
FAN ON
SET pOINT
160°F (71°C)
IMpORTANT:
W415-1013 / A / 06.05.12