English
Fault
There is leakage between the
bottom of the control panel
and the vaporiser.
The flame goes out directly
after ignition.
The heater makes a
humming sound.
There is unburnt fuel on the
burner dish.
Record the maintenance details in table A in the
appendix of this manual.
7
SPARE PARTS
Before use we advise you to have spare parts in
store, see table B in the appendix of this manual.
8
TECHNICAL INFORMATION
•
See for technical specifications table C in the
appendix of this manual.
50
Cause
14 There is leakage between
the bottom of the control
panel and the vaporiser.
15 The flue draught is too low. Check all connections in the flue. User
16 There is too much
biodiesel or vegetable oil
at start up.
40.020.952 - rev. 04 - 2011
Solution
Adjust the pressure on the seal
cord.
Replace the seal cord.
Check whether the draught
regulator is off.
Check the flue for blockage.
Reduce the number of bends.
Heighten the flue.
Isolate the flue outside the
building.
Check the flue, see "flue".
Reduce the amount of biodiesel
or vegetable oil.
Low temperatures for single
walled flue, for instance in case
of frost.
The sound will stop when the
temperature rises.
See faults: 2, 11, 12, 13 and 14.
Action
User
User
User
User
User
User
User
User
User
User
Bio Energy - US