7
SPARE PARTS
Before use we advise you to have spare parts in
store, see table B in the appendix of this manual.
8
TECHNICAL INFORMATION
•
See for technical specifications table C in the
appendix of this manual.
9
INSTALLING ACCESSORIES
9.1
Flue (fig. 7)
The heater has a flue stack connection.
1.
Push a T-piece (A) directly over the
connection (B).
2.
Push the flue pipe (C) on the T-piece.
3.
Use three screws to screw the flue pipe to the
T-piece.
Caution
The flue must meet the following
requirements.
•
The flue must be pointed upwards.
•
The flue (or any part of it) may not be
positioned horizontally. A 45° angle is
acceptable.
•
It is not allowed to lenghten the flue
connection horizontally.
•
When a pipe is used under 45°, pipe pieces
of at least 3.3 ft must be fitted in front of and
at the back of the slanting pipe.
•
The flue must stick out at least 1.6 ft above
the apex of the building.
•
Keep the vertical part at the back of the
heater as long as possible before leading it
outside through the wall.
4.
Fit the following pipe pieces.
5.
Place a cap (D) at the end of the flue.
9.2
Diameter flue
/i
Bio Energy 1
5.9 inch
10
STANDARDS AND GUIDELINES
For the standards and guidelines, go to
www.thermobile.nl.
Bio Energy - US
40.020.952 - rev. 04 - 2011
English
15