eLeCtriCaL CONNeCtiONs

Separate circuits, each must be protected by a Ground Fault
Circuit Interrupter (GFCI), are required for the pump/motor and
the RapidHeat™ Heater. Refer to the electrical specification
for each model, see Specifications. Install duplex outlets to
the studwall underneath the bathtub, at least 4" (102 mm)
above the floor or in accordance with local building or
electrical codes. Duplex outlets are not provided. Because
these units are manufactured with an electronic control panel,
no remote switch or timer is necessary.
Tubs with electronic control panels combine the electrical
requirements of the pump/motor and electronic controls into
a control box. For these units the power supply cord from the
pump/motor runs to the control box. The power supply cord
from the control box should be connected to the 20 AMP GFCI
circuit.
Before installing electrical connections, inspect the pump/
motor and heater nameplates and confirm you have 120
VAC, 20 AMP and 15 AMP service requirements. The GFCI
circuits must match these requirements. Care must be taken
to connect the 20 AMP pump/motor or control box power cord
ONLY to the 20 AMP GFCI circuit, and to connect the 15 AMP
heater power cord ONLY to the 15 AMP GFCI circuit. Do NOT
switch power cords and GFCI circuits.
Luxury WhirLPOOL iNterCONNeCtiON DiagraM
The interconnection of the Luxury Whirlpool equipment is shown in the following figure. It shows the only acceptable manner in
which the system components may be interconnected for efficient and safe operation. If the equipment is not configured as shown
in the figure, the equipment may not operate or it may result in damage to the equipment
H
G
F
Jacuzzi
Luxury Bath Series: Installation and Operation
©
A
C
B
E
With a No. 8 solid copper wire, bond the heater to the house
electrical panel or approved local bond. A bonding lug is
provided on the heater. With another No. 8 solid copper
wire, bond the pump/motor to the house electrical panel or
approved local bond. A bonding lug is provided on the pump/
motor.
At initial start-up and before each use thereafter with power
ON, push the GFCI test button on each circuit. The reset
button should pop out. Push this button in to reset. If the
interrupter fails to operate in this manner, there is a ground
current flowing or a device malfunction, indicating the
possibility of electrical shock. Turn off power and do not use
the bath until the source of the problem has been identified
and corrected.
DaNger: Risk of electric shock. Connect only to a circuit
protected by a Ground Fault Circuit Interrupter (GFCI).
CautiON: Operating the motor/pump without enough water
in the bath can cause leaking and permanent damage to the
pump. Before power is applied to the installation, make sure
the switch is in the OFF position to avoid pump damage.
D
LegeND
A. Air control valve assembly
B. System Control Module
C. Ozone Generator, Water
D. Pump-Motor, Two Speed, 115 VAC
E. Pump-motor-ozone power distribution box
F. Power supply plug, 115 VAC, 20 A
G. Control panel, Seven-button
H. Chromatherapy light
Page 18