ELECTRICAL CONNECTIONS
Caution
Electrical compartment contains live terminals, please ensure supply is isolated before
removing the cover. Any person accessing this part of the unit should be suitably trained and
competent.
Before carrying out any maintenance work, disconnect the drive and the external control
circuits from the power supply by moving the main system switch to "off". Once power has
been disconnected from the drive,
electrical cables.
Product / Compressors
2 x DY45
2 x RY100
3 x RY100
4 x RY100
5 x RY100
4PTE-7K
2 x 4PTE-7K
4PTE-7K + 4MTE-10K
2 x 4MTE-10K
4MTE-10K + 4KTE-10K
2 x 4KTE-10K
2 x 4PTE-7K + 2MME-07K
2 x 4PTE-7K + 2KME-1K
4PTE-7K + 4MTE-10K + 2MME-07K
4PTE-7K + 4MTE-10K + 2KME-1K
4PTE-7K + 4MTE-10K + 2JME-2K
2 x 4MTE-10K + 2MME-07K
2 x 4MTE-10K + 2KME-1K
2 x 4MTE-10K + 2JME-2K
2 x 4MTE-10K + 2HME-3K
4MTE-10K + 4KTE-10K + 2MME-07K
4MTE-10K + 4KTE-10K + 2KME-1K
4MTE-10K + 4KTE-10K + 2JME-2K
4MTE-10K + 4KTE-10K + 2HME-3K
2 x 4KTE-10K + 2MME-07K
2 x 4KTE-10K + 2KME-1K
2 x 4KTE-10K + 2JME-2K
2 x 4KTE-10K + 2HME-3K
wait at least 5 minutes before disconnecting the
Electrical supply
400 V / 3 ph / 50Hz
N+G
400 V / 3 ph / 50Hz
N+G
400 V / 3 ph / 50Hz
N+G
MAX amperage of
the unit
29.1 A
36.3 A
54.5 A
70.6 A
86.7 A
19.4 A
34.7 A
43.4 A
50 A
50.5 A
67.4 A
39.8 A
41.2 A
48.5 A
49.9 A
48.7 A
55.1 A
56.5 A
55.3 A
56.2 A
55.6 A
57 A
55.8 A
56.7 A
72.5 A
73.9 A
72.7 A
73.6 A
82