Profroid QUIETCO2OL MC Notice D'instruction page 82

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

COMMISSIONING
Liquid Receiver
The refrigerant charge in Transcritical mode must be maintained as close as possible
to the low level alarm.
A higher level in this mode could lead to excess charge in Subcritical operation.
Oil separator
OUTDOOR version with coalescent oil separator : the separator filter must be
replaced 24 to 36 hours at the latest after commissioning (filter for replacement
supplied)
In the case of OUTDOOR SH versions, there is no need to add an excess of oil
during commissioning, beyond the recommendations done in the chapter
"COMMISSIONING/Oil Charge" about the initial oil charge.
Indeed, in this case, any excess of oil usually leads to oil blows on the rack causing
the degradation of the compressors (breakages of valves plates / or gasket).
Nota :
If the superheat of the medium temperature consumer is too low, the MP valve will
open, which can lead to an alarm at the consumers
If the superheat at the outlet of the expansion valve is too low (4 ° K for 10 minutes),
the controller slowly increases the MP receiver pressure up to 40 bar and in this case
an overheating alarm at the control unit may appear
It may be necessary to deactivate this alarm temporarily for commissioning, but it
must be operational at the end of commissioning
Liquid level alarm
High&low level alarms
The triggering of the alarm is based on an hourly average between faulty readings
and no faults.
If the alarm is too frequent outside of a lack of refrigerant, the sampling time may
not be appropriate.
80

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières