COMMISSIONING
–
For compressors equipped with a frequency converter, the drive ensures the start-up
phase and the safety of the compressor motor. (See parameters pre-set in the drive)
–
Repeat these steps for each compressor. Check that no suspicious noise comes from
the machine.
Additional refrigerant charge
–
Very quickly, proceed with an additional refrigerant charge. Indeed, the low charge
of fluid leads to a high superheat, and therefore, to abnormally high discharge
temperatures.
–
A charge service valve is located on the filter dryer station.
Operating controls
–
Shortly after start-up, the operating conditions of the installation must be checked:
Compressors
–
The compressor must operate in its operating range. Check for each compressor
(the others being stopped):
–
the discharge pressure
–
the suction temperature
–
the discharge temperature
–
the oil level
Rotary version operating range