COMMISSIONING
For compressors equipped with a frequency converter, the drive ensures the start-up
phase and the safety of the compressor motor. (See parameters pre-set in the drive)
Repeat these steps for each compressor. Check that no suspicious noise comes from
the machine.

Additional refrigerant charge

Very quickly, proceed with an additional refrigerant charge. Indeed, the low charge
of fluid leads to a high superheat, and therefore, to abnormally high discharge
temperatures.
A charge service valve is located on the filter dryer station.

Operating controls

Shortly after start-up, the operating conditions of the installation must be checked:
Compressors
The compressor must operate in its operating range. Check for each compressor
(the others being stopped):
the discharge pressure
the suction temperature
the discharge temperature
the oil level
Rotary version operating range