CAUTION FOR SAFETY
As professional, the installer must:
–
Define the operating conditions of the refrigeration equipment under his own
responsibility regarding the design. This device needs to be incorporated in machines
conforming to the Machines Directive. Its commissioning is only authorized if it has
been incorporated in machines which fully satisfy the legal regulations.
–
Complete and adapt these recommendations, if necessary, by adding other safeties and
/or controls according to the refrigeration equipment's operating conditions.
–
Have performed all the installing, commissioning and maintenance operations by
qualified professionals and conforming with standards EN 378, EN 14276, EN 13136,
EN 13313, EN 60204 and EN 60335, the EU directives, the safety rules generally
recognized, sound engineering practice, the local regulations; as well as those which
may be set up, taking into account the evolution of the technology and the regulations.
–
If the installation, the commissioning, the operating, the maintenance are not realized
according to this operating instructions, the responsibility of Profroid cannot be
involved.
–
Completely inform the customer on the control, maintenance and follow-up of the
refrigeration equipment.
The units have been designed for 80/80/80/120bar pressure and are equipped with discharge
safety pressure switches set at 120 bars.
Any system that is designed with PS < 74 bar (R744 critical point) can risk overpressure when
it stops. When installing a QuietCO2OL MC unit to a system using a lower design pressure, the
installer is responsible for the protection of this system (for example by installing a safety valve).