The gate movements must not be interrupted (complete opening/closing).
If they are interrupted, programming will resume the next time the opening command is issued.
If indicator light
flashes, relaunch auto-programming of the leaf travel (4 full opening and closing movements).
If the indicator light
continues flashing, consult the troubleshooting guide page 16.
If the gate re-opens at the end of the closing movement, loosen and offset the gate leaf brackets slightly towards the centre of
the gate.
WARNING
Once installation is complete, it is essential to check that the obstacle detection complies with annex A of the standard EN 12 453.
5.4 Checking the position of the antenna
For optimum performance, it is essential that the antenna is
correctly positioned.
Do not cut the antenna wire.
5.5 Closing the control unit
1
Affix summary label to the back of the control unit cover.
5.6 Standby / reactivation of the control electronics
Once the self-programming process has been completed, the electronics automatically switch to standby a er 5 minutes of inactivity to save
energy.
In standby mode, all indicator lights are off.
To check if the motorisation is switched on or to check/modify the parameter setting, press the
electronics. The electronics will pass automatically to stand-by a er 5 minutes of inactivity.
5.7 Default operation
Operating your gate in sequential mode and complete opening mode
Successive presses of the same remote control button will lead to the following movements of the gate: Open, Stop, Close, Stop, Open etc.
5.8 Detecting an obstacle
When closing the gate, if an obstacle is detected (abnormal force on the motorisation), the gate stops then reopens
When opening the gate, if an obstacle is detected (abnormal force on the motorisation), the gate stops.
Antenna
2
Close the control unit and screw in the cover.
EN - Replacing the EXAVIA 500 / WISPA 800 / SGS 201SGS 400 / SGS 501 electronic unit - SOMFY
button for 2 seconds to reactivate the
9