Electrical installation
Relay output connections
5.5
Connection of relay outputs K1 and K2
Tip!
•
For switching the control signals use shielded cables and establish an HF shield termination
by PE connection.
•
For mains potential switching unshielded cables are sufficient.
•
With inductive or capacitive loads a corresponding protective circuit is required in order to
protect the relay contacts!
•
The service life of the relay depends on the type of load (ohmic, inductive or capacitive) and
the value of the switching capacity.
Relay K1
X1.2/K11
X1.2/K12
X1.2/K14
PES
The output message can be changed under C0008 or C0415/1.
84
EDK82EV903 DE/EN/FR 2.2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Function
Relay position set
NC contact relay output
Relay middle contact
NO contact relay output
HF-shield end by PE connection through shield bracket.
K11
K1
K12
K14
K21
K22
K2
K24
nc
Message
(Lenze setting)
open
TRIP
closed
TRIP
X1.2
K11
K12
K14
X1.3
K21
K22
K24
nc
8200vec261
Technical data
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
L