1)
Keypad
PC
Error
140
Faulty parameter identification Motor not connected
id1
32
Fault in motor phase
LP1
(is displayed if C0597 = 1)
182
Fault in motor phase
LP1
(is displayed if C0597 = 2)
-
DC-bus undervoltage
LU
11
Short circuit
OC1
12
Earth fault
OC2
13
Overload inverter during
OC3
acceleration or short circuit
14
Overload controller during
OC4
deceleration
15
Controller overload in
OC5
stationary operation
16
Motor overload (I
OC6
50
Heatsink temperature
OH
> +85 °C
-
Heatsink temperature
OH
> +80 °C
53
PTC monitoring (TRIP)
OH3
(is displayed if C0119 = 1 or 4)
54
Controller overtemperature
OH4
203
PTC monitoring
OH51
(is displayed if C0119 = 2 or 5)
-
DC-bus overvoltage
OU
(Warning or TRIP configurable
under C0310)
22
OUE
L
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Troubleshooting and fault elimination
Cause
•
Failure of one/several motor phase(s)
•
Motor current too low
Mains voltage too low
DC-bus voltage too low
400 V controller connected to 240 V mains
Short circuit
Excessive capacitive charging current of the motor
cable
Grounded motor phase
Excessive capacitive charging current of the motor
cable
Acceleration time too short (C0012)
Defective motor cable
Interturn fault in the motor
Deceleration time set too short (C0013)
Frequent and long overload
2
x t overload) Motor is thermally overloaded, for instance,
because of
•
impermissible continuous current
•
frequent or too long acceleration processes
Ambient temperature too high
Heatsink very dirty
Impermissibly high currents or too frequent and too
long acceleration
Motor too hot because of excessive currents or
frequent and too long accelerations
PTC not connected
Controller too hot inside
Motor too hot because of excessive currents or
frequent and too long accelerations
PTC not connected
Mains voltage too high
Braking operation
Earth leakage on the motor side
Error messages
Remedy
Connect motor
•
Check motor cables
•
Check V
boost
min
•
Connect motor to corresponding power or adapt the
motor under C0599.
Check mains voltage
Check supply module
Connect controller to the appropriate mains voltage
•
Find reason for short circuit; check motor cable
•
Check braking resistor and cable for braking resistor
Use shorter motor cables with lower charging current
Check motor, check motor cable
Use shorter motor cables with lower charging current
Deactivate earth-fault detection for testing purposes
•
Increase acceleration time
•
Check drive selection
Check wiring
Check motor
•
Increase deceleration time
•
Check size of external brake resistor
Check drive selection
•
Check drive selection
•
Check setting of C0120
Allow controller to cool and ensure better ventilation
Clean heatsink
•
Check drive selection
•
Check load, if necessary, replace defective bearings
Check drive selection
Connect PTC or switch off monitoring
•
Reduce controller load
•
Improve cooling
•
Check fan in the controller
Check drive selection
Connect PTC or switch off monitoring
Check voltage supply
•
Prolong deceleration times.
•
Operation with external brake resistor:
– Check dimensioning, connection and cable of the
brake resistor.
– Increase the deceleration times
Check motor cable and motor for earth fault (disconnect
motor from inverter)
EDK82EV903 DE/EN/FR 2.2