Supply and fan connection at the controller for a mains voltage of 400 V/500V
5.4.1

Mains connection

Both, the master and the slave must be supplied!
ƒ
0
L1
L2
L3
PE
+UG
M8
25-30 Nm
L1, L2,
L3
221-264 lb-in
M6
PE
15-20 Nm
133-176 lb-in
Fig. 5−8
Fuses and cable cross−sections for the mains supply
Type
EVF9381−EVV210
EVF9381−EVV240
EVF9381−EVV270
EVF9381−EVV300
EVF9382−EVV210
EVF9382−EVV240
EVF9382−EVV270
EVF9382−EVV300
EVF9383−EVV210
EVF9383−EVV240
EVF9383−EVV270
EVF9383−EVV300
EDKVF9383 DE/EN/FR 4.0
-UG
BR1
BR2
PE
U
V
W
40 mm
Mains connection example
BR1, BR2
Brake resistor can only be operated with the variants V270 and V300
For connection see System Manual of 9300 vector
0
Master terminals
1
Slave terminals
2)
Fuse
Master
Slave
315A
315A
315A
315A
400 A
400 A
1)
Multiple conductor; both conductors must have the same cross−section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation
l
Electrical installation
Mains connection
1
L1
L2
L3
PE
+UG
-UG
BR1
M8
25-30 Nm
L1, L2,
L3
221-264 lb-in
M6
PE
15-20 Nm
133-176 lb-in
Installation to EN 60204−1
2
L1, L2, L3 [mm
]
Master
Slave
Master
150
150
1)
1)
2 × 50
2 × 50
150
150
1)
1)
2 × 50
2 × 50
240
240
1)
1)
2 × 95
2 × 95
5
BR2
PE
U
V
W
40 mm
9300VEC035
2
PE [mm
]
Slave
95
95
95
95
150
150
87