Cable conduit seal
Item No. 97 711
wall ducts customary in trade (see illustration).
In order to seal the cable conduit inside the building the
KESSEL cover (cable conduit sealing, item No. 97711)
should be installed as protection against unpleasant odours.
Changes in direction should be carried out by means of cur-
ved fittings with a maximum bend of 30°.
Caution: Up to their final connection, all pipes should be tem-
porarily sealed with adhesive tape to prevent the ingress of
dirt while the pipes are pushed through.
Remark:
The tanks may be drilled open in the area of the domes to
produce additional connecting and ventilation lines. For this,
original drill bits and pipe duct seals by KESSEL must be
used (KESSEL drill bits DN 50 - DN 150, item No. 50100,
KESSEL pipe duct seals:
DN 50 item No. 850114
DN 70 item No. 850116
DN 100 item No. 850117
DN 125 item No. 850118
DN 150 item No. 850119
Drilling should be carried out on surfaces that are as plane
as possible.
To provide an optimum seal for the drilled hole, the clearan-
ce between the edge of the drilled hole and uneven contour
should amount to at least 15 mm so that the seal circumfe-
rentially butts evenly against the drill hole.
• Ventilation
Plants with closed cover are aerated and ventilated via the
penstock of the drainage plant. An additional ventilation line
in DN 100 can be connected to the dome. For this purpose,
the appropriate drill bit and pipe duct seal by KESSEL must
be used (see illustration page 5). KESSEL recommends the
use of an activated carbon filter to avoid any unpleasant
odours.
4. Installation and assembly
Concrete sealing
Base-
ment
wall
Wall duct customary in
trade e.g. by Steelter or
DOYMA DN 100
Gradient at least
KG-pipe DN 100
2° sloping towards the tank
Notice for EW 12 – EW 30 Inno-Cleans
The aeration tube for InnoClean PLUS systems size EW 12
to EW 20 needs to be installed on-site. The black aeration
tube should be lowered into the treatment chamber (not the
sludge chamber) using the air hose it is connected to and pla-
ced lengthwise on the base of this tank.
Analog systems are at the nominal sizes EW 22 to EW 30,
the aerator candles before filling the tanks in the 3rd Contai-
ner insert in the longitudinal direction.
Conduit pipe
Inlet
108
Seal item
No. 860 116
Seal for pipe duct
Ventil Valve
InnoClean PLUS
Tank wall InnoClean PLUS
Ventialtion pipe DN 100
Tank 1
Connection pipe
Outlet
Tank 2