Burkert 8030 HT Manuel D'utilisation page 7

Masquer les pouces Voir aussi pour 8030 HT:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 2:
Diagram flow/ rate / fluid velocity/ DN of
sensor-fitting S030 HT
gpm
m
/h
3
l/min
1000
200
3000
2000
500
100
1000
50
200
500
100
20
200
50
10
100
5
20
50
10
2
20
5
1
10
0.5
2
5
1
0.2
2
0.5
0.1
1
0.05
0.2
0.5
0.1
0.02
0.2
0.05
0.01
0.1
0.3 0.5
0.3 0.5
1
3
English
24
• Use a shielded cable with an operating tempe-
rature limit higher than +80 °C.
• Use a high quality electrical power supply (fil-
tered and regulated).
Assembling the female connector
Unscrew nut [1] of the cable gland.
2
Remove terminal block [3] from
housing [2].
3
Insert the cable into nut [1], through
seal [4], and into the cable gland and
finally through housing [2].
4
Connect the wires on terminal block
[3].
1
Position terminal block [3] in steps of
90° then put it back into housing [2],
pulling gently on the cable so that the
wires do not clutter the housing.
Tighten nut [1] of the cable gland.
English
26
DN50 (DN65)*
DN40 (DN50)*
DN32 (DN40)*
DN25 (DN32)*
DN20 (DN25)*
DN15 (DN15 or
DN20)*
DN08
DN06
5
m/s
1
3
10
5
10
30
fps
Fluid velocity
Assemble the electronic module and the sensor-fitting
according to Fig. 2.
3
Fig. 2:
Assembling the SE30 HT and the sensor-fitting
S030 HT
Wiring
danger
risk of injury due to electrical discharge
• Shut down and isolate the electrical power source
before carrying out work on the system.
• Observe all applicable accident protection and safety
regulations for electrical equipment.
protect the power supply
• Protect the power supply with a correctly rated
fuse if it is not protected by default.
Place seal [5] between the connector
and the fixed connector on the device
and then plug the 2508 connector into
5
the fixed connector.
Insert and then tighten screw [6] to
6
ensure tightness and correct electrical
contact.
Fig. 3:
Assembling the female connector type 2508
(supplied)
Fig. 4:
Pin assignment of the fixed connector, version
with pulse outputs
1
2
English
25
25
1: V+ (12-36 V DC)
2: NPN pulse output
3: 0 V DC
4: PNP pulse output
English
27
27

Publicité

Table des Matières
loading

Table des Matières