General connections KM2500
The connection of the operator to the VIVO-T101
control panel is shown as an example.
P1 P2 P3
P4 P5 P6
P15 P14 P16
P7 P8
ST1
STOP
FT1
ST2
FT2
FCA1
FCC1
VIVO-T101 Control board parts
PUL1:
Open mini-pushbutton
PUL2:
Close mini-pushbutton
SW1
Main switch
KM2500 Operator parts
FCA
Magnetic opening limit switch (Hall effect
sensor) (supplied installed and connected)
FCC
Magnetic closing limit switch (Hall effect
sensor) (supplied installed and connected)
M
Three-phase motor
Before carrying out any gate movement, ensure there is no person or
object in the radius of action of the gate and the operation mechanisms.
Fig. 5
Operator connections KM2500- control panel VIVO-T101
VIVO-T101
P11 P12
P22 P23
G7 G8
G9 G10
Courtesy
24Vac
Lamp.
LOCK
Light
The operator must be connected to the control
panel as shown in the lower diagram. The other
elements of the facility must be connected to the
control panel in line with the control panel
instructions guide.
G1
G2
G3
N
L
POWER
MOTOR1 (G2-G1-COM)
A1 operator connections:
1
Opening limit switch (FCA)
2
Limit switches common
3
Closing limit switch (FCC)
U, V, W: Motor connections
PE: Earth connection
Turning direction check
Press PUL1 (open) and PUL2 (close) to check that the
turning direction of the operator. If it is not correct,
interchange connections V and W.
INSTALLATION
KM2500
12-24
Vac/Vdc
3
P96V
TORO operator for sliding gates
67