Show/Hide Bookmarks
2
Technical data
General data/operating conditions
2
Technical data
2.1
General data/operating conditions
Standards and application conditions
Field
Conformity
Max. permissible motor
cable length
Vibration resistance
Climatic conditions
Degree of pollution
Packaging (DIN 4180)
Permissible temperature
ranges
Permissible installation
height
Volume flow of the internal
heatsink fan
Mounting positions
DC-bus operation
General electrical data
Field
Discharge current against PE
(to EN 50178)
Enclosure
Protection measures against Short circuit, earth fault (earth-fault protected during operation, limited earth-fault
Protective insulation of
control circuits
52
Values
CE
At rated mains voltage and a switching frequency of ≤ 2 kHz without additional
output filter
shielded
100 m
unshielded
200 m
EN 50178
Class 3K3 to EN50178 (without condensation, average relative humidity 85%)
VDE 0110 part 2 pollution degree 2
Transport packaging
Transport
Storage
Operation
0 ... 4000 m amsl
3
975 m
Vertically suspended
Possible for types EVF93xx-EVV210, EVF93xx-EVV240, EVF93xx-EVV270,
EVF93xx-EVV300
Values
> 3.5 mA
IP20
Shock protection to NEMA 250 type 1
protection during mains connection), overvoltage, motor stalling, motor
overtemperature (input for PTC or thermal contact)
Safe mains isolation: Double/reinforced insulation according to EN 50178 for digital
inputs and outputs
Low-Voltage Directive (73/23/EEC)
For compliance with EMC regulations, the permissible cable
For compliance with EMC regulations, the permissible cable
lengths must be changed.
-25 °C... +70 °C
-20 °C ... +60 °C
0 °C ... +50 °C
/h per device
reduce the rated output current by 2.5%/
°C above +40 °C
reduce the rated output current by 5%/
1000 m above amsl
EDKVF9383 DE/EN/FR 1.0