6. USE OF THE ECO HOT WATER
Activation of the solar circulator (model EQ 3018 ES)
In HEATING and ECO-HEATING operation, when the STT temperature
exceeds BTT by 5 °C (n03), the solar circulator starts to operate.
It will then stop in the following cases:
• STT< BTT+2°C
• STT<20°C
• BTT>70°C (n10)
Operation of the fan to replace the air.
Fan icon types
1 - Fan is running
.
Indicates that the fan is operating at high speed.
2 - Fan is running
.
Indicates that the fan is operating at low speed (function not available).
3 - If you do not see the fan icon, it means that it is switched off.
4 - Fan is not running
.
Indicates that the fan will operate at high speed when the value set
for the hot water output is reached.
5 - Fan is not running
.
Indicates that the fan is operating at low speed when the value set for
the hot water output is reached.
With the unit in any mode of operation and also in OFF, you can set the
operation of the fan after the unit has reached the set value.
Always press and hold the
key, after about 2 seconds the
will appear that relates to the ventilation mode at low speed (function
not available).
Continue to press the
key, after about 2 seconds the
pears that means that refers to high speed ventilaton.
Continuing to press and hold the
ventilation icon disappears and therefore as the relevant set value of the
temperature of the outflow water has been reached, the ventilator will
remain off.
Heat treatment hot water
(domestic hot water to inhibit and / or limit the proliferation of Legionella
in the accumulation)
The function Heat treatment hot water is disabled by default.
To turn on the Heat treatment hot water function, choose and set the
desired values for parameters g01, g02 , g03, g04
icon
icon ap-
key, after another 2 seconds the
Ventilation modes
TEMP
GB
GB
61