ATyS
Controller
OPERATION
ATyS C40
Operation
ACTIVE SOURCES
>
Description
When a basic cycle is started, the first started group is the
one who has the least worked, or the one who is defined
in the menu "source" (in programming mode).
Nevertheless, in a punctual way it is possible to force
this choice of starting up of the next group by "opera-
tion" menu
RESET OF COUNTER
>
Description
During a basic cycle, each group works during a time
defined in the "source" menu in the programming mode.
This timer can be reset punctually during a running of
the associated genset.
58
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
>
Activation
- If the LCD indicate "SAct 1", then the next "Source
Active", or the next source which will be started, will be
the source 1.
- If the LCD indicate "SAct 2", then the next "Source
Active", or the next source which will be started, will be
the source 2.
>
Activation
- If the LCD indicate "rES nO", then the timer is not
reseted.
- If the LCD indicate "rES YES", then the timer is reseted.
SOCOMEC - Réf. : 532 929 B