ATyS
Controller
OPERATION
ATyS C40
Programming
>

Frequency Menu

1 2
Threshold detection starts from the loss of source
or source return sequence.
%
Controlled value (frequency)
100
LCD
Denomination / Definition
Network 1 over frequency threshold
1 2
Network 1 over frequency threshold hysteresis
1 2
Network 1 under frequency threshold
1 2
Network 1 under frequency threshold hysteresis
1 2
Network 2 over frequency threshold
1 2
Network 2 over frequency threshold hysteresis
1 2
Network 2 under frequency threshold
1 2
Network 2 under frequency threshold hysteresis
1 2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
50
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
Over frequency threshold (oU)
Over frequency hysteresys
threshold (oUh)
Available source
t
Under frequency hysteresys
threshold (uUh)
Under frequency threshold (uU)
Setting
range
From 101
to 120 %
From 100.5
to 119.5% (< oF)
From 80
to 99 %
From 80.5
to 99.5 % (> uF)
From 101
to 120 %
From 100.5
to 119.5% (< oF)
From 80
to 99 %
From 80.5
to 99.5 % (> uF)
SOCOMEC - Réf. : 532 929 B
Default
values
105 %
103 %
95 %
97 %
105 %
103 %
95 %
97 %