Programming
>
Inputs/Outputs Menu
Inputs
Variable
Description
SSt
Start / stop transfer cycle.
Ft1
Fault input source 1. The fault led is blinking as soon as the input is active and Ft1 is displayed on LCD.
Reset when the input is de-actived (see diagram 2).
AL1
Alarm input source 1 (see diagram 1).
Ft2
Fault input source 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on
LCD. reset when the input is de-actived (see diagram 2).
AL2
Alarm input source 2 (see diagram 1).
Man
Information transfer system in manual mode. All automatic commands and test are inhibited as soon
as the input is activated.
MtF
Remote manuel re-transfer. Feature identical to manual transfer on keypad. Re-transfer from priority
source to backup source is allowed from input activation (1s front). The Mtf variable in the setup menu
must be selected (Yes) to allow input recognition.
Outputs*
Variable
Description
S1A
Source 1 available.
Output activated as soon as source 1 is considered available (similar to front led source 1).
S2A
Source 2 available.
Output activated as soon as source 2 is considered available (similar to front led source 2).
ScA
Source 1 or Source 2 available.
Output activated as soon as source 1 or Source 2 considered available (similar to one of front led
source 1or Source 2).
* Non available in IMP logic (see LOG in SETUP menu).
SOCOMEC - Réf. : 532 929 B
1 2
Controller ATyS
OPERATION