Programming
PARAMETERS CHARACTERISTICS
>
Menu Setup
1 2
LCD
Denomination
Network
nominal voltage
1 2
Network
nominal
1 2
frequency
Genset start
signal state
1 2
Manual
retransfer
1 2
"impulse" or
"contactor"
1 2
logic
Number of
auxiliary contact
1 2
Return to 0
position
1 2
Number of
permutation
1 2
counter Reset
Programming
code
1 2
Restricted
access code
1 2
modification
SOCOMEC - Réf. : 532 929 B
Definition
Phase-Neutral voltage or Phase-Phase voltage
Network nominal frequency
Normally opened or closed. The same state for the 2
sources.
Activation of the feature
Outputs control logic: impulse (IMP) or contactor (Con)
Depends on changeover technology
(switch, contactor, breaker)
Allows to go to position 0 in case of network loss
(contactor logic type)
Automatic sequences counter reset
Programming code modification
Restricted access (counters rS1 and rS2) code modification
Controller ATyS
OPERATION
Setting
Default
range
values
From 100 V to
220 V
440 V
50 Hz or 60 Hz
50 Hz
nO or nC
nO
YES or nO
nO
Imp or con
IMP
0 or 2
2
YES or nO
nO
YES or nO
nO
From 0000 to
1000
9999
From 0000 to
5000
9999
47