Control circuits
Denomination Terminals Description
Power supply L3 (104) Phase 3
1
Source
L1 (106) Phase 1
Power supply L1 (203) Phase 1
Source
2
L3 (205) Phase 3
Power supply DC DC-
Power supply 0 V
12Vdc, 24Vdc
DC+
Power supply + V dc
1
Genset
13
Genset
(1)
start signal
14
Programmable state - factory setting = NO, close to start 5A AC1 / 250 V
Control
23
Impulse mode: order to close source
(impulse,
24
Contactor mode: order to close contactor source
contactor
Breaker mode: order to close breaker source
and breaker
33
Impulse mode: order to close source
mode to
34
Contactor mode: order to close contactor source
programm)
Breaker mode: order to open breaker source
43
Impulse mode: order to close position 0
44
Contactor mode: programmable relay O1
Breaker mode: order to close breaker source
2
Genset
53
Genset
start signal
(1)
54
Programmable state - factory setting = NO, close to start
Information
301
Auxiliary contact information position 1 CA1
auxiliary
302
Programmable input 3
contacts
303
Auxiliary contact information position 2 CA2
Programmable 304
Programmable input 1
Inputs
305
Programmable input 2
Common
316
Specifique voltage supply
input
Common terminals 301 to 310
(1) Refer to programming, Setup, to modify relay state.
SOCOMEC - Réf. : 532 929 B
1
start / stop relay - 2 stable positions
2
start / stop relay - 2 stable positions
Characteristics
440 V ac (phase-phase)
maximum, 50 / 60 Hz
440 V ac (phase-phase)
maximum, 50 / 60 Hz
From 9 V dc to 30 V dc
maxi.
Dry contact
1
5 A AC1 / 250 V
1
1
2
5 A AC1 / 250 V
2
1
5 A AC1 / 250 V
2
5 A AC1 / 250 V
Do not connect to
any power supply
Do not connect to
any power supply
Do not connect to
any power supply
Controller ATyS
CONNECTIONS
Recommended
section
2
1.5 mm
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
41