Programming
>
Volt Menu
1 2
Threshold detection starts from the loss of source
or source return sequence.
%
Controlled value (voltage)
100
LCD
Denomination / Definition
Network 1 over voltage threshold
1 2
Network 1 over voltage threshold hysteresis
1 2
Network 1 under voltage threshold
1 2
Network 1 under voltage threshold hysteresis
1 2
Network 2 over voltage threshold
1 2
Network 2 over voltage threshold hysteresis
1 2
Network 2 under voltage threshold
1 2
Network 2 under voltage threshold hysteresis
1 2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
SOCOMEC - Réf. : 532 929 B
Controller ATyS
OPERATION
Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Available source
t
Under voltage hysteresys
threshold (uUh)
Under voltage threshold (uU)
Setting
range
From 102
to 120 %
From 101
to 119 % (< oU)
From 80
to 98 %
From 81
to 99 % (> uO)
From 102
to 120 %
From 101
to 119 % (< oU)
From 80
to 98 %
From 81
to 99 % (> uU)
Default
values
115 %
110 %
85 %
95 %
115 %
110 %
85 %
95 %
49