ATyS
Controller
OPERATION
ATyS C40
Programming
>
AL1 Alarm diagram 1
• An alarm is typically a warning information: fuel tank will
be empty very soon -> the genset will be stopped.
sst
Input
AL1
Start/stop order
Sensing
Start/stop order
Sensing
Position G1
Position O
Position G2
54
dtt 1
GFt 1
Cdt 1
dtt 2
< tF 1
tF 2
OSF 1 -> 2
tG 1 = 0.5xtF1 + 1xtF1 + the old tG 1
tG 2 = 1xtF2 + x + 0.5xtF1 + the old tG 2
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
• During the functionning of one supply (G1 for example),
if an alarm AL1 appears, the second supply (G2 in that
case) is started at the end of GFt1 timer. G1 genset
is then stopped after Cdt1 timer. The emergency
genset G2 will then be maintained as long as the alarm
AL1 will be present. After AL1 disappearance, the basic
cycle will take over.
dtt 1
Cdt 2
x
tF 1
OSF 2 -> 1
Cdt 1
dtt 2
Cdt 2
< tF 2
OSF 1 -> 2
SOCOMEC - Réf. : 532 929 B