9.4 SUPERVISOR PARAMETERS

MODBUS BASED (0)
ANALOG / INTEGER VARIABLES (HOLDING REGISTER)
BMS
Description
Address
40001
Adsorber Inlet Temperature
40002
Purge Air Temperature
40003
Dew Point Temperature
40008
Set Dew Point Fitted
40016
Thermal Mass Temperature
40050
Pressure Column 1
40051
Pressure Column 2
40052
Discharge Refrigerant Temperature
40067
Optional (Ambient Temperature )
40129
40130
40145
40148
40149
40150
40151
40152
40153
40154
40156
40157
40171
40179
Software Release
40180
Software Date Year
40181
Software Date Month
40182
Software Date Day
40187
40188
Operating Software
40199
Moisture Drain ON
40200
Moisture Drain OFF
40202
Modbus Address
40203
Baud Rate
40204
Money Type
40206
40212
Delay Change Filter Year
40213
Delay Change Filter Month
40214
Delay Change Filter Day
40218
Optional (Set ambient Temperature )
40219
Optional (Diff ambient Temperature )
40220
Ooptional (Delay summer Day)
40221
Ooptional (Delay summer Hour)
40222
Ooptional (Delay summer Day)
40223
Optional (Offset Dew Point )
40224
Optional (set Dew point )
40226
Optional (Diff Dew point )
40229
Working Pressure
40241
Mode Moisture Drain
40289
Default
"Read/
Variable name
Write"
0
R
ADInletTemp
0
R
PurgeAirTemp
0
R
DewpointTempDisplay
-40
R/W
SetPDP
0
R
ThermalMassTemp
0
R
Pressure_Col1
0
R
Pressure_Col2
0
R
DischRefrTemp
0
R
AmbientProbe
90
R/W
SetAt70
10
R/W
RitTc
146
R/W
SetAt
5
R/W
Set_i
0
R
TimerFaseAdsorbtionCol1
0
R
TimerFaseAdsorbtionCol2
0
R
TimerFaseHeatingCol1
0
R
TimerFaseHeatingCol2
0
R
TimerFaseCoolingCol1
0
R
TimerFaseCoolingCol2
59
R/W
SetHt40
30
R/W
SetCt40
150
R/W
SetTHeat
0
R
SW_Release
0
R
SW_Date_Year
0
R
SW_Date_Month
0
R
SW_Date_Day
8
R/W
UnitModel
2
R
OperatingSoftware
5
R/W
ParMoistureDrainModeTon
120
R/W
ParMoistureDrainModeToff
1
R/W
BMS_ADDRESS
3
R/W
BaudRate
0
R/W
MoneyType
0
R/W
SelezioneDeltaKwh
0
R
UltimoCambioFiltroAnno
1
R
UltimoCambioFiltroMese
1
R
UltimoCambioFiltroGiorno
13.0
R/W
SetTambiente
2.0
R/W
DiffTambiente
0
R/W
DeleyEstateGiorni
0
R/W
DelayEstateOre
1
R/W
DelayEstateGiorni
0
R/W
OffsetDewPoint
10
R/W
SetPointDewpoint
0
R/W
DiffDewPoint
0
R
WorkingPressure
1
R/W
ParMoistureDrainMode
0
R
NewSetPDP
ATT040
BUAD
PRO
Parity
RATE
0 = 1200
1 = 1200
2 = 4800
0 = MDBUS
NONE
3 = 9600
4 = 19200
MODBUS CONFIGURATION
Stop
Data
Holding
Bit
Bits
register
1
8
10
Offset
digital
40000