Alarm-
Display
kode
WARNING CHANGE
A30
FILTERS!!!
A31
CLOCK ALARM
WARNING CAPACITIVE
A32
MOISTURE DRAIN
A33
FRIDGE SWITCH ALARM
A34
BYPASS ALARM Fail Open
A35
BYPASS ALARM Fail Close
WARNING PROBE PRES-
A36
SURE COLUMN 1
WARNING PROBE PRES-
A37
SURE COLUMN 2
WARNING Pressure Di-
A38
scharge Failure Column 1
WARNING Pressure Di-
A39
scharge Failure Column 2
"ALARM ADSORBER Heater
Manual reset Safety
Thermostat
A40
CALL SERVICE!
""Manula Reset Reque-
sted"""
Dansk
ATT
ATT
ATT
Reset
040
060-090
140-340
Reset efter
opdatering af
X
X
X
vedligeholdel-
sesdatoen
X
X
X
NU
X
A
X
NU
NU
A
X
X
X
X
NU
X
X
A
NU
X
X
A
NU
X
X
A
NU
X
X
A
X
X
X
M
Forsinkelse
Standardbetingelser for udløsning af alarmen
1 mm
fi lterelementernes levetidsslut er nået
Beskrivelse: Kontrollér eller udskift- -urkortet- Sluk kontrolenhe-
den for at nulstille alarmen
400 sek.
AIN kapacitivt niveau
Alarm for kølekredsløbet
Hvis driften er indstillet til SOMMER, aktiveres relæet til åbning af
2 min
bypasset. Hvis det ikke åbner helt inden for 2 minutter, aktiveres
alarmen
Hvis driften er indstillet til VINTER, deaktiveres relæet til åbning
2 min
af bypasset. Hvis det ikke lukker helt inden for 2 minutter, aktive-
res alarmen
Fejl på føler til tryksøjle 1
Fejl på føler til tryksøjle 2
Hvis trykket ved afslutningen af udtømningsfasen er > 3 bar
Hvis trykket ved afslutningen af udtømningsfasen er > 3 bar
Indgreb fra sikkerhedstermostaten
ATT040
Stop
Stop Tørrean-
Alarmrelæ
Kompressor
læg
N
N
Aktiv
N
N
 Aktiv
N
N
 Aktiv
J
N
Aktiv
Ja: driften
N
forbliver
Aktiv
VINTER
Ja: driften
N
forbliver
Aktiv
SOMMER
N
N
Aktiv
N
N
Aktiv
N
N
Aktiv
N
N
Aktiv
N
N
Aktiv
11 / 12