EDS 3000 IO-Link
block, earthing the block via the hydraulic system is sufficient. When installing using a
Minimess hose, the housing must be earthed separately (e.g. with a screened cable).
CAUTION:
The EDS 3000 must be fitted using a suitable open-end wrench
(across flats 27) on the hexagon nut of the pressure connection.
Inappropriate installation methods, such as manually fitting above the housing can
damage the housing or even cause the device to fail completely, due to the
rotatability of the EDS 3000.
Additional installation suggestions which, from experience, reduce the effect of
electromagnetic interference:
• Make line connections as short as possible
• Use shielded lines (e.g. LIYCY 4 x 0.5 mm²)
• The cable screening must be fitted by qualified personnel subject to the ambient
conditions and with the aim of suppressing interference.
• Keep the unit well away from the electrical supply lines of power equipment, as well as
from any electrical or electronic equipment causing interference.
5
Control elements of the EDS 3000
The
and
keys can be used to select the next or previous menu options. They can
also be used to set values.
• One step back in menu
• Decrease value
Edition: 2014-11-06
Display of
Pressure unit
4-digit
Digital display
LED-Display of
the active switching point
LED display constantly lit: Switch in SIO mode
LED display flashing: Switch in SDCI mode
Buttons for setting
Switching points, switch-back points
and additional functions
• One step forward in menu
• Increase the value
HYDAC ELECTRONIC GMBH
5
Part No.: 669897 E