Release on opening and closing limit switches.
0 = no release
21
10 = maximum release
For light gates, it reduces the bending of the leaf.
If active, it provides maximum acceleration at the start
22
0 = inactive
1 = active
23
M1 leaf delay during closing from open gate.
Sets the encoder type
0 = virtual encoder
24
1 = physical encoder
NOTE: the value depends on the type of motor selected.
Determines the type of automation on which the control unit is
installed
1 = DUO24
25
2 = RUN24
3 = DO NOT USE
4 = DO NOT USE
5 - TESTING AND COMMISSIONING THE AUTOMATION SYSTEM
The system must be tested by a qualified technician, who must per-
form the tests required by the relevant standards in relation to the
risks present, to check that the installation complies with the relevant
5.1 - Testing
All system components must be tested following the procedures
described in their respective operator's manuals
ensure that the recommendations in Chapter 1 - Safety Warnings
- have been complied with
check that the gate or door is able to move freely once the
automation system has been released and is well balanced,
meaning that it will remain stationary when released in any position;
5.2 - Commissioning
Once all (and not just some) of the system devices have passed
the testing procedure, the system can be commissioned;
the system's technical dossier must be produced and kept for
10 years. It must contain the electrical wiring diagram, a drawing
or photograph of the system, the analysis of the risks and the
solutions adopted to deal with them, the manufacturer's declaration
of conformity for all connected devices, the operator's manual for
every device and the system maintenance plan:
fix a dataplate with the details of the automation, the name of
the person who commissioned it, the serial number and year of
construction and the CE marking on the gate or door:
also fit a plate specifying the procedure for releasing the system
by hand:
0
0
1
0/1
1
regulatory requirements, especially the EN12453 standard which
specifies the test methods for gate and door automation systems.
check that all connected devices (photocells, sensitive edges,
emergency buttons, etc.) are operating correctly by performing
gate or door opening, closing and stop tests using the connected
control devices (transmitters, buttons or switches);
perform the impact measurements as required by the EN12453
standard, adjusting the control unit's speed, motor force and
deceleration functions if the measurements do not give the
required results, until the correct setting is obtained.
draw up the declaration of conformity, the instructions and
precautions for use for the end user and the system maintenance
plan and consign them to the end user;
ensure that the user has fully understood how to operate the
system in automatic, manual and emergency modes;
the end user must also be informed in writing about any risks and
hazards still present;
WARNING
After detecting an obstacle, the gate or door
stops during its opening travel and automatic closure is disabled;
to restart operation, the user must press the control button or use
the transmitter.