Overrun Time:
Added operation time of water pump after Demand OFF.
Swimming pool speed: (Not available for YUTAKI Cascade Controller)
Selection of the % for the pump speed when using Swimming pool.
Minimum ON Time:
Minimum time of the water pump ON. Only when Economic mode is active (DSW)
Minimum OFF Time:
Minimum time of the water pump OFF. Only when Economic mode is active (DSW)
Pump Setup:
This option allows user to select hydraulic configuration of the system when hydraulic separator
is used (Option available only when there is Hydraulic separator configured.).
• Standard: WP2 is connected after WP3 by means an hydraulic separator or directly by means
Hitachi mixing kit accessory. Whenever WP2 is switched ON, WP3 is also switched ON in
order to transfer heat to C2.
• Parallel: WP2 is directly connected to the buffer tank in parallel with WP3. Operation of WP3
is independent of the operation of WP2. When this configuration is used, Hitachi mixing kit
accessory cannot be used.
PMEN0597 rev.1 - 06/2023
Stop conditions:
• Standard
• Thermo-OFF: The water pump stops
after Thermo-OFF. (DSW5 pin 4 ON).
1
90