Code
Text
Incorrect indoor unit address setting
35
System
36
System
Abnormality picking up circuit for protec.
38
System
41
Indoor
42
Outdoor
43
Outdoor
Low pressure increase abnormality
44
Outdoor
Very high discharge pressure protection
45
Outdoor
Multiple Origins
47
Multiple Origins
Activation of overcurrent protection
48
Abnormal operation of the current sensor
51
Inverter
Protection of the Inverter PCB (Outdoor)
53
Inverter
Excessive temperature of the Inverter PCB
54
Inverter
Abnormal operation of Inverter PCB (OU)
55
Inverter
Activating the protection of the fan motor
57
Outdoor
5B
Outdoor fan
Activation of over current protection
Outdoor fan
Abnormality in current detection circuit
5C
202
Indoor
Sub room controller stops answering
203
Indoor
Indoor unit stops answering to controller
204
Indoor
EE
Compressor
PMEN0597 rev.1 - 06/2023
Origin
Retry stop code
Incorrect indoor unit combination
High pressure switch overload
Pressure ratio decrease
Pressure ratio increase
Excessively low suction pressure
Wrong settings of the controller
Compressor protection
Duplication of indoor unit number, number of indoor units over specifications.
-
-
Failure of indoor unit PCB, incorrect wiring, connection to PCB in indoor unit.
-
-
-
-
-
Overload (obstruction of HEX, short circuit) mixture of inert gas, Excessive Refrigerant.
-
Shortage or leakage of refrigerant, piping clogging, expansion valve close-locked, fan motor locked.
-
Overload, overcurrent. Failure of Inverter PCB, heat exchanger clogged, locked compressor. EVI/EVO failure.
-
Incorrect wiring of current sensor. Failure of control PCB or Inverter PCB.
-
Inverter module (IPM, DIP-IPM) and Inverter PCB abnormality. Failure of compressor, clogging of heat exchanger.
-
-
-
-
-
-
-
-
Loose, disconnected, broken or short-circuited connector
-
Compressor failure. This alarm code appears when the following alarms 02, 07, 08, 45, 47 occur three times within 6 hours.
-
Main factors
Heat Exchanger Clogging. Fan Motor Failure.
Failure of DIP-IPM, IPM or Inverter PCB.
2
118