◆ Anti Legionella function
NOTE
In case anti legionella treatment has not been possible to achieve within a time lapse of 6 hours
since the moment it has been trigered, anti legionella treatment is released and normal operation
can be resumed.
1.18.6 Swimming Pool configuration
PMEN0597 rev.1 - 06/2023
Status of anti legionella operation (enabled/deactivated).
Specified day for anti legionella operation.
Specified time of the day for anti legionella operation.
Setting for domestic hot water temperature in anti
legionella operation.
Duration of shock treatment. Between 10 to 60 minutes.
Status:
Enable or disable swimming pool.
Set input 3, output 1 and sensor 2. (See section
"1.18.11 Inputs, Outputs and Sensors
Setting temperature:
Adjustment of the swimming pool water temperature
setting.
• Range: 24 ~ 33°C
Offset temperature: The setting temperature is increased
by the indicated parameter.
configuration")