Télécharger Imprimer la page

Samson TROVIS 3730-1 Notice De Montage Et De Mise En Service page 162

Publicité

Positioner 3730-41/51cdefghijk
Equipment markings
II 2G Ex ia IIC T* Gb
II 2D Ex ia IIIC T80°C Db
Electrical Ratings
Circuit
Circuit no.
Terminal no.
V
or U
max
i
I
or I
max
i
P
i
C
i
L
i
Rated values
Circuit
Circuit no.
Terminal no.
V
or U
max
i
I
or I
max
i
P
i
C
i
L
i
Rated values
* For connection to NAMUR switching amplifier acc. to IEC 60947-5-6
Circuit
Circuit no.
Terminal no.
U
0
I
0
P
0
C
i
L
i
Rated values
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals Ltd. Voyager Place, Maidenhead, Berkshire, SL6 2PJ. United Kingdom
T: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail:
F UKEX 020 (Jan/21)
15-46
to UK-Type Examination Certificate No. FM21UKEX0202X
Signal Circuit
Signal Circuit
Foundation™
(PROFIBUS PA)
Fieldbus
1
+11 / -12
24 V
360mA
1.04 W
5 nF
10 µH
Binary input
(24 V DC)
5
+87 / -88
30 V
100 mA
1 W
Negligible
Negligible
U
= 24 V DC
N
External position
Binary input
sensor
6
Pins p9, p10, p11
8.61 V
55 mA
250 mW
SCHEDULE
Inductive limit
FISCO
switches
2
3
+11 / -12
+41 / -42
17.5 V
16 V
380 mA
25 mA or 52 mA
5.32 W
64 mW or 169 mW
5 nF
60nF
10 µH
100 µH
* U
= 8.2 V, R
N
kΩ
7
+85 / -86
5.88 V
1 mA
5,32 W
5 nF
10 µH
atex@fmapprovals.com www.fmapprovals.com
Forced
venting
4
+81 / -82
28 V
115 mA
1 W
5.3 nF
Negligible
= 1
i
EB 8484-1 FR
Page 11 of 16

Publicité