Installation Manual for Apparatus certified by FM Approvals for use in Hazardous
Classified Locations
Electrical rating of Intrinsically Safe / Non-Incendive Apparatus for installation in Hazardous Locations
Table 1: Maximum values
Circuit
Signal
Circuit
Circuit No.
Terminal No.
+11 / -12
V
or U
28 V
max
i
I
or I
115 mA
max
i
P
1 W
i
C
16.3 nF
i
L
negligible
i
Rated values
I
= 4 mA...20 mA
N
* For connection to NAMUR switching amplifier acc. to IEC 60947-5-6
Note: Entity / Nonincendive Field Wiring Parameters must meet the following requirements:
U
or V
≤ U
or V
0
OC
i
C
or C
≥ C
+ C
a
O
i
Cable
The correlation between Temperature Class and permissible ambient temperature range T
in Table 2.
Table 2:
Temperature Class
T4
T6
For operation with Inductive Limit Switches (3793-130.....15 or 3793-130.....16) used with
I
/I
= 52 mA and Pi = 169 mW the correlation between Temperature Class and permissible ambient
max
i
temperature range is shown in Table 3.
Table 3:
Temperature Class
T4
T6
Revision Control Number: 0 / August 2022
EB 8484-1 FR
Position
Transmitter
1
2
+31 / -32
28 V
115 mA
1 W
11.1 nF
negligible
U
= 24 V DC
N
/ I
or I
≤ I
or I
/ P
≤ P
max
0
SC
i
max
0
/ L
or L
≥ L
+ L
a
O
i
Cable
Addendum Page 1
Limit Switches
Limit Switches
Inductive
3 and 4
+41 / -42
and
+51 / -52
16 V
25 mA or 52 mA
64 mW or 169 mW
71.1 nF
100 µH
* U
= 8.2 V
* U
N
R
= 1 kΩ
i
or P
i
max
Permissible ambient temperature T
-40 °C ≤ T
≤ + 80 °C
a
-40 °C ≤ T
≤ + 55 °C
a
Permissible ambient temperature T
-40 °C ≤ T
≤ + 70 °C
a
-40 °C ≤ T
≤ + 45 °C
a
Addendum to EB 8484-1 EN
Software
5 and 6
+45 / -46
and
+55 / -56
16 V
52 mA
169 mW
12.2 nF
negligible
= 8.2 V
N
R
= 1 kΩ
i
is shown
a
a
a
15-25