Télécharger Imprimer la page

DAB Esybox Serie Instructions Pour L'installation Et L'entretien page 73

Publicité

13.3.9. Self-reset of error conditions
For some malfunctions and blockage conditions, the system attempts automatic self-reset.
The auto self-reset procedure concerns in particular:
"BL"
Blockage due to water lack
"PB"
Blockage due to line voltage outside specifications
"OT"
Blockage due to overheating of the power stages
"HL"
Blockage due to too high liquid temperature
For example, if the system is blocked due to water lack, the device automatically starts a test procedure to check whether the machine
is really left definitively and permanently dry. If during the sequence of operations an attempted reset is successful (for example, the
water comes back), the procedure is interrupted and normal operation is resumed.
Table 13 shows the sequences of the operations performed by the device for the different types of blockage.
Display indication
BL
PB
OT
HL
OC
13.4. Operation with control unit
The pump, alone or in a pumping unit, can be connected via radio communication to an external unit hereinafter referred to as the control
unit. Depending on the model, the control unit offers various functions.
Possible control units are:
Esy I/O
The combination of one or more pumps with a control unit allows you to use:
Digital Inputs
Relay outputs
Remote Pressure Sensor
Modbus communication protocol
In the following, we will indicate with the term control unit functionality, the set of functions listed above and made available by the
various types of control unit
13.4.1. Functionality available from the control box
The available features are listed in the table below.
Opto-isolated digital inputs
Output relay with NO contact
Remote Pressure Sensor
Parameters available in version KIWA
Automatic resets of error conditions
Description
Blockage due to water lack
Blockage due to line voltage outside
specifications
Blockage due to overheating of the
power stages
Blockage due to too high liquid
temperature
Blockage due to motor overload
Table 22: Self-reset of blockages
Feature
Modbus
Table 23: Functionality available from the control box
ENGLISH
"OC"
Blockage due to motor overload
"BP1"
Blockage due to fault of the pressure sensor
"BP2"
K
Blockage due to fault of the Kiwa pressure sensor
Automatic reset sequence
- One attempt every 10 minutes for a total of 6 attempts.
- One attempt every hour for a total of 24 attempts
- One attempt every 24 hours for a total of 30 attempts
- It is reset when it returns to a specific voltage.
- It is reset when the temperature of the power stages returns
within the specifications.
If the device detects a liquid temperature that is too high, the
pump remains blocked and "HL" is indicated.
The error state begins as soon as the problem is detected and
ends automatically once the liquid temperature is within the
allowed values.
- One attempt every 10 minutes for a total of 6 attempts.
- One attempt every hour for a total of 24 attempts.
- One attempt every 24 hours for a total of 30 attempts.
67
Esy I/O

Publicité

loading