MR ECOTAP VPD MD&C Instructions De Service page 103

Mécanisme d'entraînement et unité de contrôle
Masquer les pouces Voir aussi pour ECOTAP VPD MD&C:

Publicité

Address (no
Name
offset)
0, 1
Device number
2
Capacitor health
3
Input voltage (data value = 2 x measured value;
example: measured value = 125.5 V => data value
= 251)
4
Voltage capacitor (data value = 10 x measured
value; example: measured value = 10.6 V => data
value = 106)
5
Software version year (YY)
6
Software version month (MM)
7
Software version day (DD)
8
Motor pause before next tap-change operation
(data value = 10 x measured value; example:
measured value = 3 sec. => data value = 30)
9
Status activation Modbus RTU (1 = active, 0 = in-
active)
10
Remaining time to the next PreCheck
11
Internal datapoint
12, 13
Input voltage
14, 15
Buffer voltage
36600
Tap position
Tableau 25: Input Register (sans option DS)
9.4.3 Input Register (sans option DS)
Type
Unit
Decimal
places
SINT32
-
0
UINT16
%
0
UINT16
V
0
UINT16
V
0
UINT16
-
0
UINT16
-
0
UINT16
-
0
UINT16
seconds
1
UINT16
-
0
UINT16
minutes
1
UINT16
-
-
FLOAT32
V
-
FLOAT32
V
-
UINT16
-
-
6117331/06 FR Protocole poste de conduite  
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO
Others
R
R
R
R
-
R
-
R
R
R
R
R
R
R
R
R
-
R
-
R
-
-
-
R
-
R
-
R
103