Pilotage io-link

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Designation
State in normal opera-
tion
Off
COMM
Illuminates green
Flashes green (1 Hz)
Flashes green (2 Hz)
Flashes red (1 Hz)
Illuminates red
Flashes red (2 Hz)
Off
11.4 Pin assignment
Table 6: Pin assignment of M12 plug connector X7I1 for IO-Link type A and IO-
Link type AB
Pin
Meaning
IO-Link type A
1
L+
2
N. c.
2
1
3
L-
3
4
4
CQ (IO-Link data)
Table 7: Pin assignment of M12 plug connector X7I1 for IO-Link type B
Pin
Meaning
1
L+ 24 V DC 0.02 A
2
2L+ 24 V DC max. 3 A
2
1
3
L-
3
5
4
4
CQ (IO-Link data)
5
2L-
12 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
13 Troubleshooting
13.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections. See g 9. Service.
• Settings. See
g 14. Technical
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
AVENTICS™ XVES | 570096-BAL-001-AA | English
Meaning
No valve supply voltage.
IO-Link interface is not connected to the IO-
Link master.
Operating state
IO-Link master is connected, IO-Link commu-
nication has not been started.
Pre-operating state
IO-Link master is connected, IO-Link commu-
nication has not been started.
SIO mode
No connection to IO-Link master, IO-Link
communication has not been started.
Communication error with valves, automatic
recovery
No connection to valves.
No connection to IO-Link master.
No valve supply voltage.
IO-Link interface is not connected to the IO-
Link master.
IO-Link type AB
L+ 24 V DC 0.02 A
UA +24 V DC max. 3 A
L-
CQ (IO-Link data)
data.
g 4.3 Returning the
product.
13.2 Malfunction types
Error
Possible cause
No output pressure at the
• No power supply con-
valves
nected to the product.
See
• No supply pressure avail-
able.
Output pressure too low
Supply pressure too low.
Power supply for the product
not sufficient.
Air is audibly escaping
Leakage between product
and supply.
Pneumatics incorrectly con-
nected.
UL/UA LED flashes/illumi-
Valve supply voltage is below
nates green/red
the lower tolerance limit.
COMM LED is off
IO-Link master is not con-
nected.
COMM LED is flashing green
IO-Link interface connection
switched off.
IO-Link communication has
not been started.
14 Technical data
This section contains an excerpt of the most important technical data. Further
technical data can be found on the product page in the Emerson store.
General
Dimensions
Weight
Material
Degree of contamination
Relative humidity
Ambient temperature for storage
min. ... max.
Ambient temperature during operation
min. ... max.
Max. length of communication cables
Max. number of valves
Max. height above sea level
Vibration resistance for EN 60068-2-6
wall mounting
Shock resistance for EN 60068-2-27 wall
mounting
Electrics
Degree of protection according to
EN 60529 / IEC 60529
Supply voltage
Valve supply voltage
Connection type
Permissible ripple
Standards and directives complied with
Standard / directive Description
EMC directive
Electromagnetic compatibility of electric products and electronic
2014/30/EU
products
EN 60204-1
Safety of machinery – Electrical equipment of machines, Part 1: Gen-
eral requirements
EN 61000-6-2
Electromagnetic compatibility (EMC); part 6-2: Generic standards –
interference immunity for industrial environments
Remedy
Apply power supply on plug
connector X7I1.
g 11.3.1 LED
display.
Check power supply polarity.
Switch on system compo-
nent.
Connect supply pressure.
Increase supply pressure.
Check LED on the product.
Apply sufficient power sup-
ply.
Check the supply connection.
Check the pneumatic connec-
tion.
Check power supply on plug
connector X7I1.
Check connection of the IO-
Link master on plug connec-
tor X7I1.
Configure IO-Link interface
connection and switch on.
Start IO-Link communication.
Specifications
45 mm x 97.2 mm x 27.25 mm
0.062 kg
Fiberglass reinforced polyamide
2
95 %, non-condensing
-25 ... 80 °C
-10 ... 50 °C
20 m
24 (48 coils)
2000 m
±0.35 mm displacement at 10 Hz ... 60 Hz,
5 g acceleration at 60 Hz ... 150 Hz
30 g with 18 ms duration,
3 shocks each direction
Specifications
IP65 when assembled
18 ... 30 V DC
24 V DC ±10 %
M12 A-coded, 4 pin or 5 pin
5 %
18