Gas Installation
General
All gas handling and installation should be performed by a qualified service technician or installer .
Gas build-up during line purge could ignite . Ensure adequate ventilation . Ensure there are no ignition sources,
sparks, or open flames .
Do not change the gas valve setting! The fireplace gas valve has been preset at the factory .
Installing an external manual gas valve before connection to the fireplace is necessary .
Make sure to check for gas leaks before lighting the fireplace for the first time . Do not use an open flame to
check for gas leaks .
This appliance and its individual shut off valve must be disconnected from gas supply piping system during any
pressure testing of that system at test pressures more than ½ psig (3 .5 kPa) .
This appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig
(3 .5 kPa) .
Have the gas supply line installed in accordance with local codes, if any . If not available, follow ANSI 223 .1 .
Installation should be done by a qualified installer approved and/or licensed as required by the locality (In the
Commonwealth of Massachusetts Installation must be performed by a licensed plumber or gas fitter) .
1 . Move the appliance into position and secure it to the wall using the back or side mount .
2 . Install a manual gas valve before the connection to the fireplace appliance automatic valve .
3 . Connect the gas line to the fireplace . The appliance is designed to accept a ½" (13 mm) gas supply .
4 . Connect the gas supply in accordance to local codes, CAN/CSA-B149 .1 in Canada or to the current National
Fuel Gas Code, ANSI 2223 .1 / NFPA 54 in the United States .
5 . Check for gas leaks using non-corrosive commercially available leak-check solution before operating the gas
appliance .
6 . Measure and document gas pressure below:
Inlet ___ W .C . Burner (Manifold) ___ W .C . Ensure the Min/Max inlet pressure matches the table below .
7 . Verify minimum pressures when other household gas appliances are operating .
8 . Lighting the fireplace for the first time may take some time until the line is purged .
! NOTE:
Do not place the gas valve or controls above the level of the burner .
Inlet Pressure
53
!
RISK OF FIRE OR EXPLOSION!
Natural Gas
7 .0" W .C .
!
RISK OF FIRE OR EXPLOSION!
High pressure will damage valve . Low pressure could cause explosion .
WARNING
Propane
11 .0" W .C .
WARNING