Clearances
Minimum Combustible Clearances from Vent Pipe
Horizontal Vent Pipe Clearances
A minimum clearance of 3" (76 mm) to the top and 1" (25 mm) to the sides and bottom of the vent pipe on all
horizontal runs, to combustibles, is required .
Vertical Vent Pipe Clearances
A minimum of 1" (25 mm) around the vent pipe on all vertical runs to combustibles is required, except for
clearances in appliance enclosures .
Horizontal Vents must have a minimum 1/4" (6 mm) rise per 1-foot run towards the termination .
• Never allow the vent to run downward . A downward slope can trap heat and become a possible fire hazard .
• Maintain vent clearance to combustibles as detailed above .
• DO NOT pack airspace with insulation or other materials . Failure to keep insulation or other materials away from
vent pipe could cause overheating and fire .
• This fireplace is not designed to be load-bearing or support weight of any architectural framing . All framing
should be self-supported, supported by the back wall, side wall, or ceiling . Attempting to
mount framing to a fireplace subjects' glass to unsupported weight and could result in damage to fireplace or
breakage of glass . Improper framing or mounting to unit will void product warranty . Please consult Faber directly
for additional questions or concerns about framing options .
43