3.
Remove the screws fixing the fan deck Fig. 9.
4.
Rotate the lockers of the fan deck Fig. 10.
5.
Take out the fan deck Fig. 11.
6.
Replace the fan deck and mount the components back in the opposite sequence.
Fig. 7
Fig. 10
All EURAPO EBH units are provided with dynamically balanced fan decks,
in order to reduce noise at minimum levels and to avoid vibrations. For this
reason, EURAPO suggest to ask for a new complete and balanced fan deck,
instead of replacing single components (for ex. only the electric motor).
EURAPO is not responsible for any problems due to modifications or
replacements executed on original fan decks.
7.4.2 REVERSING THE POSITION OF THE WATER CONNECTIONS
For maintenance operations turn off the unit and wait for some minutes. Always use protection gloves.
The water connections can be reversed on site, from the left to the right side, before
installing the unit, by following the instructions below.
1.
Disconnect and remove the electric box Par. 7.4.1 Fig. 7.
2.
Remove the bottom closure panels Fig. 12 and Fig. 13.
Fig. 8
Fig. 11
Fig. 9
EN
1
2
3
4
5
6
7
8
9
10
+